22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
AS*A07/ 09/ 12/ 14LGC
104°C
101°C
110°C
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the control of the
compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped
and the indoor unit LED starts blinking.
(Table 17 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 18 : Current Release Operation Value / Release Value)
05-17
[ Heating ]
OT (Control / Release)
5.5A/ 5.0A
6.0A/ 5.5A
7.0A/ 6.5A
7.0A/ 6.5A
5.5A/ 5.0A
7.0A/ 6.5A
7.5A/ 7.0A
8.5A/ 8.0A
17°C
12°C
OT : Outdoor Temperature
5°C
AS*A07/ 09LGC
OT (Control / Release)
17°C
12°C
OT : Outdoor Temperature
5°C
AS*A12LGC
OT (Control / Release)
3.5A/ 3.0A
4.0A/ 3.5A
5.5A/ 5.0A
4.0A/ 3.5A
5.0A/ 4.5A
6.0A/ 5.5A
46°C
42°C
OT : Outdoor Temperature
AS*A07/ 09LGC
OT (Control / Release)
46°C
42°C
OT : Outdoor Temperature
AS*A12LGC
7.0A/ 6.5A
9.0A/ 8.5A
10.0A/ 9.5A
10.0A/ 9.5A
OT (Control / Release)
17°C
12°C
OT : Outdoor Temperature
5°C
AS*A14LGC
4.5A/ 4.0A
6.0A/ 5.5A
8.5A/ 8.0A
OT (Control / Release)
46°C
42°C
OT : Outdoor Temperature
AS*A14LGC
[ Cooling ]
Summary of Contents for ASYA12LGC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 15: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 41: ......
Page 66: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 77: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2008 Printed in Japan ...