2. PRECAUTION FOR INSTALLATION
06-02
Precaution for installation
The pipe must be properly pressure rated for R410A
The pipe must be an air-conditioning refrigerant pipe.
Flare and flare nuts
Diameter
1/4
”
(6.35mm)
3/8
”
(9.52mm)
1/2
”
(12.7mm)
Refrigerant
R410A
R22
/R407C
R410A
R410A
A
9.1
9.0
13.2
13.0
16.6
16.2
B
13
12
20
15
13
20
C
12
11
16
12.5
19
16
Nut width
17
22
26
24
Always use the flare nut that is packed
with the product.
Do not use existing (for R22) pipes
•
Be sure to use new pipes when replacing
conventional (R22) model with HFC
(R407C, R410A)
model.
•
If you use existing pipes, it may cause
resolution of compressor oil by remaining
mineral oil.
3/8
”
(15.88mm)
R410A
22
29
19.7
25
R22
/R407C
R22
/R407C
R22
/R407C
19.4
23
20
27
3/4
”
(19.05mm)
R410A
24
36
24
29
R22
/R407C
23.7
29
24
Material
Nominal diameter
(in)
1/4"
3/8"
1/2"
5/8"
3/4"
7/8"
1 1/8" 1 1/4"
1 1/2"
1 3/8"
1"
6.35
9.52 12.70 15.88 19.05 22.22
28.58 31.75
38.10
34.92
25.40
Outside diameter
(mm)
Wall thickness
(mm)
0.8
0.8
0.8
1.0
1.2
1.0
1.0
1.1
1.3
1.2
1.0
1) Allowable tensile stress 33 (N/mm );
>=
2
2) Allowable tensile stress 61 (N/mm ); 3) Design pressure 4.2MPa.
>=
2
JIS H3300-C1220T-H or equivalent
2)
COPPER
JIS H3300-C1220T-O or equivalent
1)
COPPER
3)
Pipe diameter, recommended material and wall thickness
A
C
B
Summary of Contents for ASYA12LGC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 15: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 41: ......
Page 66: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 77: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2008 Printed in Japan ...