 WARNING

•  The appliance shall be installed, operated and stored in a room with a 

fl

 oor area larger 

than X m².

Amount of refrigerant charge 

M (kg)

Minimum room area 

X (m

2

)

 1.22

-

1.22 < M 

 1.23

1.45

1.23 < M 

 1.50

2.15

1.50 < M 

 1.75

2.92

1.75 < M 

 2.0

3.82

2.0 < M 

 2.5

5.96

2.5 < M 

 3.0

8.59

3.0 < M 

 3.5

11.68

3.5 < M 

 4.0

15.26

(IEC 60335-2-40)

•  Installation of this product must be done by experienced service technicians or profes-

sional installers only in accordance with this manual. Installation by non-professional 
or improper installation of the product might cause serious accidents such as injury, 
water leakage, electric shock, or 

fi

 re. If the product is installed in disregard of the 

instructions in this manual, it will void the manufacturer’s warranty.

•  Do not turn on the power until all work has been completed. Turning on the power be-

fore the work is completed can cause serious accidents such as electric shock or 

fi

 re.

•  If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant 

is exposed to a direct 

fl

 ame, it may produce a toxic gas.

•  Installation must be performed in accordance with regulations, codes, or  standards for 

electrical wiring and equipment in each country, region, or the installation place.

•  Do not use means to accelerate the defrosting process or to clean, other than those 

recommended by the manufacturer.

•  This appliance is not intended for use by persons (including children) with reduced 

physical, sensory or mental capabilities, or lack of experience and knowledge, unless 
they have been given supervision or instruction concerning use of the appliance by a 
person responsible for their safety. Children should be supervised to ensure that they 
do not play with the appliance.

•  To avoid danger of suffocation, keep the plastic bag or thin 

fi

 lm used as the packaging 

material away from young children.

•  The appliance shall be stored in a room without continuously operating ignition 

sources (for example: open 

fl

 ames, an operating gas appliance or an operating 

electric heater).

•  Do not pierce or burn.
•  Be aware that refrigerants may not contain an odour.

 CAUTION

•  Read carefully all safety information written in this manual before you install or use the 

air conditioner.

•  Install the product by following local codes and regulations in force at the place of 

installation, and the instructions provided by the manufacturer.

•  This product is part of a set constituting an air conditioner. The product must not be 

installed alone or be installed with a device not authorized by the manufacturer.

•  Always use a separate power supply line protected by a circuit breaker operating on 

all wires with a distance between contact of 3 mm for this product.

•  To protect the persons, earth (ground) the product correctly, and use the power cable 

combined with an Earth Leakage Circuit Breaker (ELCB).

•  This product is not explosion proof, and therefore should not be installed in an explo-

sive atmosphere.

•  To avoid getting an electric shock, never touch the electrical components soon after 

the power supply has been turned off. After turning off the power, always wait 5 min-
utes or more before you touch the electrical components.

•  This product contains no user-serviceable parts. Always consult experienced service 

technicians for repairing.

•  When moving or relocating the air conditioner, consult experienced service technicians 

for disconnection and reinstallation of the product.

•  Do not touch the aluminum 

fi

 ns of heat exchanger built-in the indoor or outdoor unit to 

avoid personal injury when you install or maintain the unit.

•  Do not place any other electrical products or household belongings under the product. 

Condensation dripping from the product might get them wet, and may cause damage 
or malfunction to the property.

•  Be careful not to scratch the air conditioner when handling it.

AIR CONDITIONER
Duct type

Contents

1. SAFETY 

PRECAUTIONS 

.................................................................. 1

1.1. Precautions for using R32 refrigerant ......................................... 2

2. PRODUCT 

SPECIFICATION 

............................................................. 4

2.1. Installation tools .......................................................................... 4
2.2. Accessories ................................................................................ 4
2.3. Pipe requirement ........................................................................ 4
2.4. Electrical requirement ................................................................. 4
2.5. Optional parts ............................................................................. 5

3. INSTALLATION 

WORK 

..................................................................... 5

3.1. Selecting an installation location ................................................ 5
3.2. Installation dimensions ............................................................... 5
3.3. Installing the unit ......................................................................... 5
3.4. Drain installation ......................................................................... 7
3.5. Pipe installation .......................................................................... 9
3.6. Electrical wiring ......................................................................... 10
3.7. Remote controller setting .......................................................... 13

4.  OPTIONAL INSTALLATION WORK ................................................ 13

4.1. Optional kit installation .............................................................. 13
4.2. External input and output .......................................................... 13
4.3. Remote sensor (Optional parts) ............................................... 14
4.4. IR receiver unit (Optional parts) ................................................ 14
4.5. Auto louver grille (Optional parts) ............................................. 14
4.6. Other optional parts .................................................................. 14
4.7. Optional parts cable binding ..................................................... 15

5.  REMOTE CONTROL INSTALLATION ............................................. 15

5.1. Group control ............................................................................ 15
5.2. Multiple remote control ............................................................. 16
5.3. DIP switch 101 setting .............................................................. 16
5.4. Simultaneous multi-system operation ....................................... 17

6. FUNCTION 

SETTING...................................................................... 17

6.1.  Function details ........................................................................ 17

7. TEST 

RUN 

....................................................................................... 19

7.1.  Check items .............................................................................. 19
7.2. Operation method ..................................................................... 19

8. FINISHING 

...................................................................................... 19

9. CUSTOMER 

GUIDANCE 

................................................................ 19

10. ERROR CODES 

.............................................................................. 19

NOTES:

  This manual describes how to install the air conditioner described above. Handling 

and installation shall only be done by professionals as outlined in this manual.

1. SAFETY PRECAUTIONS

•  Be sure to read this manual thoroughly before installation.
•  The warnings and precautions indicated in this manual contain important information 

pertaining to your safety. Be sure to observe them.

•  Hand this manual, together with the operating manual, to the customer. Request the 

customer to keep them on hand for future use, such as for relocating or repairing the 
unit.

 WARNING

Indicates a potentially or imminently hazardous situation 
which, if not avoided, could result in death or serious injury. 

 CAUTION

Indicates a potentially hazardous situation that may result in 
minor or moderate injury or damage to property.

INSTALLATION MANUAL

PART No. 9374342532

[Original instructions] 

For authorized service personnel only.

English

Deutsch

Français

Español

Italiano

E

λλη

vIk

ά

Português

Ру

сский

Türkçe

Türkçe

9374342532_IM.indb   1

9374342532_IM.indb   1

2018/12/11   10:11:28

2018/12/11   10:11:28

Summary of Contents for ARXG-KLLAP Series

Page 1: ...installed in an explo sive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable parts Always consult experienced service technicians for repairing When moving or relocating the ...

Page 2: ...ntly far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks No Smoking signs shall be displayed 2 6 Ventilated area Ensure that the area is in the open or th...

Page 3: ...ior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical handling equipment is available if required for handling refriger ant cylinders all personal protective equipment is available and being us...

Page 4: ... fall water leakage electric shock or fire Keep the Installation manual in a safe place and do not discard any other accessories until the installation work has been completed The following installation accessories are supplied Use them as required Name and Shape Q ty Name and Shape Q ty Operating manual 1 Cable tie large 4 Operating manual CD ROM 1 Cable tie medium 3 Installation manual This manu...

Page 5: ...rol cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Decide the mounting position with the cus...

Page 6: ...sed Air Intake grille Locally purchased Side inlet Side outlet Duct Insulation material Locally purchased Aluminum tape Aluminum tape Tapping screw for flange connection M4 x 10mm Locally purchased Flange Locally purchased Flange Locally purchased Air Duct Locally purchased Air Intake grille Locally purchased Bottom inlet Side outlet Duct Locally purchased Intake grille Locally purchased Air Air O...

Page 7: ...OOD VP25 O D 32 mm or more Rise Air bleeding PROHIBITED Trap Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less When drain pump is not used natural drainage CAUTION Set Drainage function setting DIP switch 101 1 in 5 3 DIP switch 101 setting If the drain pump is not used please replace with the...

Page 8: ...se as in the figure 2 Be sure to connect Drain pipe with adhesive polyvinyl chloride so that there is no leakage Applying area of adhesive Joint pipe Locally purchased Drain pipe VP25 Locally purchased 4 mm or less CAUTION Do not connect to the Drain hole with adhesive Using adhesive may cause damage and water leaks 3 After installing the Drain hose check if the drainage is smooth CAUTION To preve...

Page 9: ...ipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break The pipes are shaped by your hands Be careful not to collapse them Bend R70 mm or more with a pipe bender Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them anymore Do not bend or stretch the pipes more tha...

Page 10: ...ard Imperfect installation may cause a fire Use ring terminals and tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause heavy damage inside the unit CAUTION Be careful not to generate a spark as follows for using a flammable refrigerant Do not remove the fuse while the power is on Do not disconnect the wiring while the power is on I...

Page 11: ...ultaneous triple 18 model only Wired remote controller cable 3 wire type only Connection cable Indoor unit Primary Indoor unit Secondary Outdoor unit Earth Ground line Control line Power line Wired remote controller Remote controller cable Bus wire Locally purchased remote controller cable Max length 500 m Junction box Locally purchased Earth Ground line Red White Black Indoor unit Secondary Indoo...

Page 12: ...1 8 12 to 18 3 6 4 Connection wiring CAUTION Be careful not to mistake the power supply cable and connection wires when install ing Install so that the wires for the remote controller will not come in contact with other connection wires 1 Remove the control box cover 2 Connect the connection cable Cover Screw Connection cable Y1 Y2 TO REMOTE CONTROL UNIT Ex IN Y3 1 2 Y1 Y2 TO REMOTE CONTROL UNIT E...

Page 13: ...eration Stop mode or Forced stop mode can be selected with function setting of indoor unit A twisted pair cable 22 AWG should be used Maximum length of cable is 150 m 492 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Y1 Y2 TO REMOTE CONTROL UNIT Ex IN Y...

Page 14: ...onnected set the function setting of indoor unit as indicated below Function Number 30 Set the Setting Number to 00 Default Function Number 31 Set the Setting Number to 02 Refer to 6 FUNCTION SETTING for details about Function number and Setting value 4 4 IR receiver unit Optional parts For the installation method please refer to the installation manual of IR receiver unit 4 4 1 Connection method ...

Page 15: ...REMOTE CONTROL UNIT Ex IN Y3 1 2 1 2 3 SW100 a 2 wire type DIP switch RC AD SW Factory setting 00 Since the remote controller address settings are automatically configured you do not need to configure them If configuring manually it is necessary to configure both the indoor unit and the remote controller For details please refer to the remote controller installation manual b 3 wire type DIP switch...

Page 16: ...nnection cable Remote controller cable Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 Outdoor unit 4 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7 5 2 Multiple remote control Up to 2 remote controllers can be used to operate one indoor unit CAUTION Multiple installation method described above is prohibited to combine 3 Wired type with 2 Wired Type ...

Page 17: ...ly 3 Set the primary and secondary Remote controller setting 1 Turn on all of the indoor units 2 Set the primary and secondary settings Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary Function Number Setting Value Primary 51 00 Secondary 01 3 After completing the function settings turn off all of the indoor units and then turn them back on If err...

Page 18: ... changed Select the appropriate custom code Factory setting Function number Setting value Setting description 44 00 A 01 B 02 C 03 D External input control Operation Stop mode or Forced stop mode can be selected Factory setting Function number Setting value Setting description 46 00 Operation Stop mode 1 01 Setting prohibited 02 Forced stop mode 03 Operation Stop mode 2 Room temperature sensor swi...

Page 19: ...in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Cleaning and maintenance of the product and other items such as air filters and air louvers if applicable 3 Give the operating and installation manuals to the customer 4 If the indoor unit custom code is changed and the ...

Page 20: ...5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor error Sub cool Heat Ex gas outlet temp sensor error 8 3 Liquid pipe temp sensor error 8 4 Current sensor error 8 6 Discharge pressure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection Error ...

Reviews: