Active Filter Failure
[Checking points]
Check the following points and locae the cause in the outdoor unit.
[Cause]
(1) Incorrect wiring
(2) Active Filter Module defective
(3) PC Board defective
(4) DC voltage detectiion circuit defective
[First Step]
Measure the DC voltage at terminals (between Electrolytic Capacitor and discharge resistance)
in the Inverter Controller Assy, and make sure it is lower than DC5V.
If it is higher than 5V, wait until the discharging is over.
Open the Inverter Controller Assy
and check if there is abnormal points.
Incorrect wiring > Correct and recheck
(Incorrect wiring, Parts touched, Parts broken)
Parts touched > Correct and recheck
Parts broken > Change the broken part
Turn on the power and press TEST button
on Remote Control.
Is the outdoor fan rotating?
Operate the unit for certain time and
measure the terminal voltage of the
The unit is normal.
discharge resistance.
Is the DC voltage between 350 to 425V?
Recheck
Operate the unit for certain time and
Yes(Operating) >
Check completed
check if the compressor is operating.
No(Not operating) > Return to the start
Check point (1)
Yes(Normal)
Go to Check point (2)
No(Abnormal)
Check point (2)
Yes(Rotating)
Go to Check point (3)
No(Not rotating)
Check point (3)
Yes(Within range)
No(Out of range)
ACTPM or PCB defective > Replace Main PCB
ACTPM or PCB defective > Replace ACTPM or
Main PCB.
(Replace only ACTPM if Main PCB was replaced
at Check point (2).)
07-10
Summary of Contents for AOYR24LCC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 9: ...D I M E N S I O N S Model ASYA30LCC 02 02 Unit mm inch 998 39 1 4 228 9 320 12 5 8 ...
Page 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 14: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 17: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 38: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 69: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ...REPLACEMENT PARTS 09 06 Model AOYR24LCC ...
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 108: ...REPLACEMENT PARTS 09 39 Model AOYR30LCT PROCESS Wiring ...
Page 109: ...REPLACEMENT PARTS 09 40 Model AOYR30LCT PROCESS Wiring ...
Page 110: ...REPLACEMENT PARTS 09 41 Model AOYR30LCT PROCESS Wiring ...
Page 111: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 116: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...