(3)  Press 

ENTER

 (TEST RUN) switch for more than 3 seconds.

POWER

MODE

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

(L7)

TEST RUN LED will light on.

If the compressor is operating at starting the test run, the compressor will stop and, 

 

after a while, the test run will start.
Either of the above LOW NOISE or PEAK CUT LED will light on during the test run if 

 

local setting function is selected.

(4)  Confirm operating status.

(5)  Press 

ENTER

 (TEST RUN) switch again.

POWER

MODE

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

(L7)

TEST RUN LED lights off, and TEST RUN stops.

Test run will finish after about 60 minutes automatically. At the same time, TEST RUN 

 

LED will light off.
Test run may be stopped before operating for 60 minutes if an error occurs after a 

 

starting test run. 

s

d

11. PUMP DOWN

 WARNING

Never touch electrical components such as the terminal blocks or reactor except the 

switch on the display board. It may cause a serious accident such as electric shock.

 CAUTION

Perform the pump down operation before disconnecting any refrigerant pipe or electric 

cable.

Collect refrigerant from the service port or the 3-way valve if pump down cannot be 

performed.

In case of a group control system installation, do not turn the power off pump down is 

completed in all outdoor units. 

(Group control system installation described in “SPECIAL INSTALLATION METHODS” 

in the installation manual of the indoor unit.)

Operate 

PUMP DOWN

 switch on the display board in the manner described below.

LED display part

PUMP DOWN

switch

Charging port

Charging port cap

3-way valve

Service hose

Terminal blocks

Service port

Service port cap

Service hose

Reactors

11.1. Preparation for pump down

Confirm that the power is off, and then open the service panel.

11.2. Pump down procedure

(1)  Check the 3-way valves (both at the liquid side and gas side) are opened.

(2)  Turn the power on.

POWER

MODE

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

(L7)

(3)  Press 

PUMP DOWN

 switch for 3 seconds or more after 3 minutes after power on.

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

(L7)

LED display lights on as shown in the above figure, and the fans and the 

compressor start operating.

(4)  LED display will change as shown below about 3 minutes after the compressor 

starts. Fully close the 3-way valve on the liquid pipe side at this stage.

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

(L7)

If the valve on the liquid pipe side is not closed, the pump down cannot be 

 

performed.

(5)  When LED display changes as shown in the below figure, close the 3-way valve on 

the gas pipe side tightly. 

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

(L7)

If the valve on the gas pipe side is not closed, refrigerant may flow into the piping 

after the compressor stops.

Step (5)

Closing direction

Step (4)

Hexagon wrench

Liquid pipe

Gas pipe

Closing direction

(6)  LED display changes after 1 minute as shown in the figure below.

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

(L7)

Fans and compressor stop automatically.

If the pump down is successfully completed (the above LED display is shown), the 

outdoor unit remains stopped until the power is turned off.

(7)  Turn the power off.

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

(L7)

PUMP DOWN is completed.

Notes:

To stop pump down, press the 

 

PUMP DOWN

 switch again.

To start the pump down again after the compressor is automatically stopped due to an 

 

error, turn the power off and open the 3-way valves. Wait 3 minutes, turn the power on 

and start the pump down again.
When starting the operation after completion of the pump down, turn the power off, 

 

and then open the 3-way valves. Wait 3 minutes, turn the power on and perform a test 

run in the “COOL” operation mode.

9379069274-04_IM.indb   15

28/11/2555   10:57:18

Summary of Contents for AOYG36LATT

Page 1: ...utorizado MANUALE DI INSTALLAZIONE UNITÀ ESTERNA tipo a 3 fasi A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τριφασικού Τύπου Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Tipo trifásica Apenas para pessoal de assistência autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ 3 фазного типа Только для авторизованного обслу...

Page 2: ...ain the unit Do not place any other electrical products or household belongings under indoor unit or outdoor unit Dripping condensation from the unit might get them wet and may cause damage or malfunction of your property 2 ABOUT THE UNIT d 2 1 Precautions for using R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle If air en...

Page 3: ...rant pipe connections or other areas Touching the refrigerant directly can cause frostbite If a refrigerant leak occurs during operation immediately vacate the premises and thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas The basic installation work procedures are the same as conventional refrigerant models However pay careful attention to the ...

Page 4: ...tion route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Observe the installation space specifications that are shown in the figures Keep the same space at rear air intake Provide the same space for the air intake at the rear of the outdoor unit If the installation is not performed according to the specifications...

Page 5: ...low If overturning prevention is required purchase the necessary commercially available items Bolt 20 mm Nut Base Fix securely with bolts on a solid block Use 4 sets of commercially available M10 bolt nut and washer 4 PIPE SELECTION 4 1 Selecting the pipe material CAUTION Do not use existing pipes Use pipes that have clean external and internal sides without any contamination which may cause troub...

Page 6: ...ference H1 Indoor unit to outdoor unit m 30 Max height difference H2 Indoor unit to indoor unit m 0 5 View Example L2 L3 L4 L1 H1 H2 1 For the standard pipe diameter 4 4 Connectable pipe diameter and max piping length The figures enclosed by a thick lined frame indicate the standard pipe diameter and max piping length 4 4 1 Single type installation Capacity Btu h class 36 000 45 000 54 000 Pipe di...

Page 7: ...erant piping branches Branch pipes are twin or triple type for concurrent operation and may be used for piping between the outdoor and indoor units Select a twin or triple type branch pipe and purchase it before starting the installation work Shorten the length of branch pipes from a branch to indoor unit as short as possible Maximum length within 20 m Branch pipes shall be connected by welding br...

Page 8: ...art of Blank cap is sealed for protection Fasten blank cap tightly after opening valves Table A Blank cap mm in Tightening torque N m kgf cm 6 35 1 4 20 to 25 200 to 250 9 52 3 8 20 to 25 200 to 250 12 70 1 2 25 to 30 250 to 300 15 88 5 8 30 to 35 300 to 350 19 05 3 4 35 to 40 350 to 400 Operating the valves Use a hexagon wrench size 4 mm Opening 1 Insert the hexagon wrench into the valve shaft an...

Page 9: ...s 19 05 3 4 15 m 25 m 35 m g m Liquid 12 70 1 2 None 1 000 g 2 000 g 100 g m Gas 15 88 5 8 19 05 3 4 1 Refer to View in the table of 4 3 1 Single type installation Simultaneous operation multi type Twin L1 L2 L3 2 Pre charge length Triple L1 L2 L3 L4 3 Pre charge length 2 Refer to View in the table of 4 3 2 Simultaneous operation multi type installation 3 Refer to View in the table of 4 3 2 Simult...

Page 10: ... power factor improvement condenser Instead of improving the power factor the condenser may overheat Be sure to perform the earthing grounding work Do not connect earthing grounding wires to a gas pipe water pipe lightning rod or earthing grounding wire for a telephone Connection to a gas pipe may cause a fire or explosion if gas leaks Connection to a water pipe is not an effective earthing ground...

Page 11: ...s are provided for wiring Fig A Knock out holes are provided 2 each in the same size in front lateral and rear sides Fig B Fig A Fig B Installation method of One touch bush Please fix the One touch bush accessory as shown in the figure below Front connection Lateral connection Rear connection One touch cable bush Accessories One touch cable bush Accessories One touch cable bush Accessories Pipe co...

Page 12: ...the wiring is complete s d 7 PIPE INSTALLATION 2 WARNING Install the insulated pipes so that they do not touch the compressor 7 1 Installing insulation Use an insulation on the refrigerant pipes to prevent condensation and dripping Fig A Determine the thickness of the insulation material by referring to Table A Table A Selection of insulation for using an insulation material with equal heat transm...

Page 13: ...EAK CUT L5 L6 L7 Orange Lights on during Peak cut function when local setting is activated Lighting pattern of L5 L6 and L7 indicates peak cut level _ Refer to 9 LOCAL SETTING Switch Function or operation method SW1 DIP switch For selecting cooling or heating during test operation Positions 2 to 4 of DIP switch are not used SW2 Push switch To switch between Local setting and Error code display SW3...

Page 14: ...AT Lower COOL ENTER TEST RUN switch 10 2 1 Operating procedures for the test run 1 Check the 3 way valves both at the liquid side and gas side are opened 2 Set the operation mode to COOL or HEAT POWER MODE ERROR TEST RUN PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 L7 In the first test run be sure to set the operation mode to COOL The operation mode cannot be switched between COOL and HEAT durin...

Page 15: ... valves both at the liquid side and gas side are opened 2 Turn the power on POWER MODE ERROR TEST RUN PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 L7 3 Press PUMP DOWN switch for 3 seconds or more after 3 minutes after power on ERROR TEST RUN PUMP DOWN LOW NOISE PEAK CUT POWER MODE L1 L2 L3 L4 L5 L6 L7 LED display lights on as shown in the above figure and the fans and the compressor start opera...

Page 16: ... 4 PFC AD detection error 2 6 4 PFC hardware error 2 6 5 IPM error Trip terminal L error 2 6 8 Rush current limiting resister temp rise protection 2 7 1 Discharge temp sensor error 2 7 2 Compressor temp sensor error 2 7 3 Heat Ex middle temp sensor error 2 7 3 Outdoor unit Heat Ex liquid temp sensor error 2 7 4 Outdoor temp sensor error 2 7 7 Heat sink temp sensor error 2 7 7 PFC heat sink temp se...

Page 17: ......

Reviews: