- 58 -
DUC
T TYPE
ARYG18-5
4LHT
B
P
DIP switch setting
•
Remote controller address setting (SW100)
When operating a number of indoor units by using a wired remote controller, DIP switch setting
for assigning unit number to each indoor unit is required.
DIP switches are normally set to make the unit number 00.
•
Switch 1: Setting change prohibited (SW101)
•
Switch 2: Setting change prohibited (SW101)
•
Switch 3: Fan delay setting (SW101)
When the indoor unit is stopped while operating in conjunction with auxiliary heater, the indoor
unit fan operation will continue for 1 minute.
Remote
controller
address
DIP switch number
Factory
setting
1
2
3
4
00
OFF
OFF
OFF
OFF
♦
01
ON
OFF
OFF
OFF
02
OFF
ON
OFF
OFF
03
ON
ON
OFF
OFF
04
OFF
OFF
ON
OFF
05
ON
OFF
ON
OFF
06
OFF
ON
ON
OFF
07
ON
ON
ON
OFF
08
OFF
OFF
OFF
ON
09
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON
Switch 3
Fan delay
Factory setting
ON
Enabled
OFF
Disabled
♦
00
01
02
Remote controller address
Indoor unit
Remote controller
Summary of Contents for AOYG18LBCA
Page 24: ... 18 DUCT TYPE ARYG18 54LHTBP 5 Wiring diagrams 5 1 Models ARYG18LHTBP and ARYG24LHTBP ...
Page 25: ... 19 DUCT TYPE ARYG18 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Page 96: ... 90 OUTDOOR UNIT AOYG18 54LB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Page 97: ... 91 OUTDOOR UNIT AOYG18 54LB 4 2 Model AOYG30LBTA ...
Page 98: ... 92 OUTDOOR UNIT AOYG18 54LB 4 3 Model AOYG36LBTA ...
Page 99: ... 93 OUTDOOR UNIT AOYG18 54LB 4 4 Models AOYG45LBTA and AOYG54LBTA ...