![Fujitsu AOYG18LBCA Technical Manual Download Page 114](http://html.mh-extra.com/html/fujitsu/aoyg18lbca/aoyg18lbca_technical-manual_2344273114.webp)
- 108 -
O
U
T
D
OOR UNIT
AOY
G
18-
54LB
Type of
protection
Protection form
Model
AOYG45LBTA
AOYG54LBTA
Circuit protection
Current fuse
(Filter PCB)
250 V, 30A
250 V, 10A × 2
250V, 3.15 A
Current fuse
(Main PCB)
250 V, 3.15 A
Fan motor
protection
Thermal protection program
Activate
122±9°C
Fan motor stop
Reset
116+10/-9°C
Fan motor restart
Compressor
protection
Terminal protection program
(Compressor temp.)
Activate
108°C
Compressor stop
Reset
80°C
Compressor restart
Thermal protection program
(Discharge temp.)
Activate
110°C
Compressor stop
Reset
After 7 minutes
Compressor restart
High pressure
protection
Pressure switch
Activate
4.2±0.1 MPa
Compressor stop
Reset
3.2±0.15 MPa
Compressor restart
Pressure sensor
Heating
Activate
4.1 MPa
Compressor stop
Reset
After 3 minutes
Compressor restart
Thermal protection
program
(Heat exchanger
temp.)
Cooling
Activate
67°C
Compressor stop
Reset
63°C
Compressor restart
Low pressure
protection
Pressure sensor
Cooling
Activate
0.12 MPa or less (for 5 minutes)
Compressor stop
Reset
0.15 MPa
Compressor restart
Summary of Contents for AOYG18LBCA
Page 24: ... 18 DUCT TYPE ARYG18 54LHTBP 5 Wiring diagrams 5 1 Models ARYG18LHTBP and ARYG24LHTBP ...
Page 25: ... 19 DUCT TYPE ARYG18 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Page 96: ... 90 OUTDOOR UNIT AOYG18 54LB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Page 97: ... 91 OUTDOOR UNIT AOYG18 54LB 4 2 Model AOYG30LBTA ...
Page 98: ... 92 OUTDOOR UNIT AOYG18 54LB 4 3 Model AOYG36LBTA ...
Page 99: ... 93 OUTDOOR UNIT AOYG18 54LB 4 4 Models AOYG45LBTA and AOYG54LBTA ...