background image

Self-diagnosis function table (Flashing LED Display)

Applicable model : ASY9LSACW,  ASY12LSACW

* Detailed Trouble Display (secondary level) can be indicated by pressing Test Operation button.

Error

Operation

Timer

Error

Operation

Timer

Serial Signal

Normal

1 sec

Serial reverse signal error

0.1sec

0.5sec

Normal Serial Reverse Signal can not be

Error

blinking at operation start up

blinking

2 times

received more than 10 seconds

>>Releases when it becomes normal

Signal reverse signal error

0.1sec

0.5sec

Normal Serial Reverse Signal can not be

during operation

blinking

3 times

received more than 7 sec (after receiving
effective reverse transfer signal)
>>Releases when it becomes normal

Serial forward signal error

0.1sec

0.5 sec

Normal Serial Forward Signal can not be

at operation start up

blinking

4 times

received more than 10 sec

>>Releases when it becomes normal

Serial forward signal error 

0.1sec

0.5sec

Normal Serial Forward Signal can not be

during operation

blinking

5 times

received more than 10 sec ( after receiving
effective forward transfer signal)
>>Releases when it becomes normal

Indoor unit

0.5sec

0.1sec Indoor Temperature

0.1sec

0.5sec

Thermister detection value is open when

Thermister

2 times

blinking Thermister Open

blinking

2 times

AC plug is inserted

error

>>Releases when value becomes normal

Pipe Thermister

0.1sec

0.5sec

Thermister detection value is open or short

Open or Short

blinking

3 times

when AC plug is inserted

>>Releases when value becomes normal

Outdoor unit

0.5sec

0.1sec Discharge Thermister

0.1sec

0.5sec

Thermistor detection value is open or short

Thermister

3 times

blinking Open or Short

blinking

2 times

 

error

>>Outdoor unit stops
   Releases when it becomes normal

Heat Exchanger

0.1sec

0.5sec

Thermistor detection value is open  

Thermister Open

blinking

3 times

>>Outdoor unit stops
  Releases when it becomes normal

Outdoor Temperature

0.1sec

0.5sec

Thermistor detection value is open or short

Thermistor Open or Short

blinking

4 times

 

>>Outdoor unit stops
  Releases when it becomes normal

Indoor unit

0.5sec

0.1sec Forced Automatic SW

0.1sec

0.5sec

Forced Auto SW is ON for more than

control error

4 times

blinking welded

blinking

2 times

10 seconds continuously

>>Error is indicated while it is ON
 Normal Operation other than error indition

Main Relay welded

0.1sec

0.5sec

Serial Reverse Signal is received 1 min. 

blinking

3 times

after Main relay becomes OFF

>>Error is indicated while serial reverse
  signal is input on normal operation
Normal operation except error indication

Power interruption error

0.1sec

0.5sec

50/60Hz is not detected after 2 seconds of

blinking

4 times

power ON.

>>Error is indicated and unit is stopped

Trouble Display (primary)

Detailed Trouble Display (by Test Button)

Detailed Error Item

In

do

or

In

do

or

In

do

or

O

utr

oo

r

O

utd

oo

r

O

utd

oo

r

In

do

or

In

do

or

E R R O R   C O N T E N T S

5

2004.10.07

Summary of Contents for AOY12LSAC

Page 1: ...ndoor unit Outdoor unit ASY9LSACW AOY9LSAC ASY12LSACW AOY12LSAC C O N T E N T S SPECIFICATIONS DIMENSIONS REFRIGERANT SYSTEM DIAGRAM CIRCUIT DIAGRAM DISASSEMBLY ILLUSTRATION PCB CIRCUIT DIAGRAM PARTS LIST 1 2 3 4 7 ERROR CONTENTS 5 9 12 STANDARD ACCESSORIES 14 ...

Page 2: ... is not charged in the outdoor unit at the factory DIMENSIONS TYPE Hermetic type 4 pole 3 phase DC brushles motor DISCRIMINATION 80206680 REFRIGERANT R410A g r p m r p m 950 1100 POWER SOURCE V 230 HI SPEED MED SPEED INDOOR UNIT LO SPEED QUIET C 1 350 H 1 420 C 1 150 H 1 200 C 950 H 1 000 C 740 H 900 C 1 400 H 1 470 C 1 200 H 1 290 C 1 000 H 1 110 C 820 H 980 OUTDOOR UNIT 830 INDOOR UNIT H x W x D...

Page 3: ...D I M E N S I O N S Models ASY9LSACW AOY9LSAC 2 2004 10 07 ASY12LSACW AOY12LSAC 540 120 272 302 780 55 250 535 10 280 790 230 ...

Page 4: ...CIRCUIT DIAGRAM INDOOR UNIT OUTDOOR UNIT Models ASY9LSACW AOY9LSAC ASY12LSACW AOY12LSAC 3 2004 10 07 ...

Page 5: ...dels ASY9LSACW AOY9LSACW ASY12LSACW AOY12LSACW 2 pass 2 pass Indoor heat exchanger Outdoor heat exchanger Capillary tube Pulse motor valve 2way valve 3way valve Muffler Compressor Accumulator 4way valve Strainer Dryer 4 2004 10 07 ...

Page 6: ...ister 0 1sec 0 5sec Thermister detection value is open or short Open or Short blinking 3 times when AC plug is inserted Releases when value becomes normal Outdoor unit 0 5sec 0 1sec Discharge Thermister 0 1sec 0 5sec Thermistor detection value is open or short Thermister 3 times blinking Open or Short blinking 2 times error Outdoor unit stops Releases when it becomes normal Heat Exchanger 0 1sec 0...

Page 7: ...linking 3 times start up or at 56 seconds after Fan mode is selected Permanent stop Refrigerant 0 5sec 0 1sec Discharge Temperature 0 1sec 0 5sec Discharge Temperature protection cycle error 7 times blinking abnormal blinking 2 times Discharge temperature is 110degC operated 2 times Permanent stop Cooling High Pressure 0 1sec 0 5sec High pressure rise protection Outdoor abnormal rise blinking 3 ti...

Page 8: ...TART REMOTE CONTROL CUSTOM CODE GREEN GREEN TERMINAL BOARD BLUE RED WHITE BROWN BLACK GRAY GRAY THERMAL FUSE WHITE WHITE WHITE WHITE WHITE POWER SOURCE 220 240V 50Hz GREEN YELLOW INDICATOR PCB EZ 00219HSE D F I C 1 uPD780024SGB X09 CONTROLLER PCB ASEMBLY MAIN PCB ASY9LSACW EZ 00219HSE C ASY12LSACW EZ 0021CHSE C INDOOR PRINTED CIRCUIT BOARD CIRCUIT DIAGRAM 7 2004 10 07 ...

Page 9: ...2 117 N200500K SC 10 55JH POWER SOURCE 220 240V 50Hz AOY12LSAC AOY9LSAC CONTROLLER PCB ASSEMBLY MAIN PCB AOY9LSAC EZ 002LHUE C AOY12LSAC EZ 002GHUE C OUTDOOR PRINTED CIRCUIT BOARD CIRCUIT DIAGRAM 8 2004 10 07 ...

Page 10: ...D I S A S S E M B LY I L L U S T R AT I O N Models ASY9LSACW ASY12LSACW 9 2004 10 07 ...

Page 11: ...Models ASY9LSACW ASY12LSACW 10 2004 10 07 ...

Page 12: ...Models AOY9LSACW AOY12LSACW 11 2004 10 07 ...

Page 13: ...17 9310102008 9306628017 Part No 32 Cover Switch 9311863014 33 Evaporator Total Assy 9311495017 36 Joint Pipe Assy E 9311497011 37 9304607007 38 Holder Evaporator L Holder Evaporator R 9309982017 39 9309983014 40 Water Seal 9310721001 42 Air Seal 9310611005 43 Terminal 9701955077 46 Step Motor 9900139025 48 Fan Motor Assy 9601351016 51 9312058013 52 Bracket Panel 9310001004 61 1 Flow Control Panel...

Page 14: ... 138 Separate Wall 9311013013 9311013013 23 Inverter PCB Assy 9705092020 9705092013 344 4 Way Valve 9900047016 9900047016 24 Thermistor Discharge 9704219060 9704219060 527 Protective Net 9310980019 9310980019 28 Solenoid Coil 9970033018 9970033018 734 Panel Top Painted 9310338063 9310338063 Emblem 9312633012 9312633012 Inverter capacitor 9704594013 9704594013 Fan capacitor 9900042011 9900042011 Ou...

Page 15: ...Shape Part No ASY9LSACW ASY12LSACW Wall hook bracket Remote control unit Battery penlight Cloth tape 9312752010 9312058013 0600185534 9310519004 0700076046 Tapping screw 4 x 25 STANDARD ACCESSORIES 14 2004 10 07 ...

Page 16: ...0303G2168 ...

Reviews: