background image

En-8

4.  PIPE INSTALLATION - 1

4. 1.  Flare connection (pipe connection)

 

CAUTION

Do not use mineral oil on a flared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

While welding the pipes, be sure to blow dry nitrogen gas through them.

The maximum lengths of this product are shown in the table. If the units are further 

apart than this, correct operation cannot be guaranteed.

Flaring

•  Use special pipe cutter and flare tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that the cuttings will not enter the pipe and remove 

any burrs.

(3)  Insert the flare nut (always use the flare nut attached to the indoor and outdoor 

units respectively) onto the pipe and perform the flare processing with a flare tool. 

Leakage of refrigerant may result if other flare nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

L

Check if [L] is flared uniformly 

and is not cracked or scratched.

Pipe

A

B

Die

Pipe outside  

diameter [in. (mm)]

Dimension A [in. (mm)]

Dimension B  

0

-  0.4

 

[in. (mm)]

Flare tool for R410A, 

clutch type

1/4 (6.35)

0 to 0.020 (0 to 0.5)

3/8 (9.1)

3/8 (9.52)

1/2 (13.2)

1/2 (12.70)

5/8 (16.6)

5/8 (15.88)

3/4 (19.7)

3/4 (19.05)

15/16 (24.0)

•  When using conventional flare tools to flare R410A pipes, the dimension A should 

be approximately 0.020 in. (0.5 mm) more than indicated in the table (for flaring 

with R410A flare tools) to achieve the specified flaring. Use a thickness gauge to 

measure the dimension A.

Pipe outside  

diameter  

[in. (mm)]

Width across flats

of Flare nut  

[in. (mm)]

1/4 (6.35)

11/16 (17)

3/8 (9.52)

7/8 (22) 

1/2 (12.70)

1 (26)

5/8( 15.88)

1-1/8 (29)

3/4 (19.05)

1-7/16 (36)

Width across flats

4. 1. 1.  Bending pipes

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of 

curvature of 4 in. (100 mm) or more.
If the pipe is bent repeatedly at the same place, it will break.

• 

If pipes are shaped by hand, be careful not to collapse them.

•  Do not bend the pipes at an angle of more than 90°.
•  When pipes are repeatedly bent or stretched, the material will harden, making it 

difficult to bend or stretch them any more.

•  Do not bend or stretch the pipes more than 3 times.

4. 1. 2.  Pipe connection

 

CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit 

correctly. If the centering is improper, the flare nut cannot be tightened smoothly.  

If the flare nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the outdoor unit pipe until immediately before 

connecting the connection pipe.

After installing the piping, make sure that the connection pipes do not touch the 

compressor or outer panel. If the pipes touch the compressor or outer panel, they will 

vibrate and produce noise.

(1)   Detach the caps and plugs from the pipes. 
(2)   Center the pipe against the port on the outdoor unit, and then turn the flare nut 

by hand.

To prevent gas leakage, coat the flare 
surface with alkylbenzene oil (HAB).
Do not use mineral oil.

(3)   Attach the connection pipe.

Flare nut

Connection pipe 

(Liquid)

Connection pipe 

(Gas)

Flare nut

3-way valve (Gas)

2-way valve 

(Liquid)

(4)   When the flare nut is tightened properly by your hand, use a torque wrench to 

finally tighten it.

Holding wrench

Connection pipe

Torque wrench

Body side

 

CAUTION

Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to 

tighten the flare nut correctly.

•  Outer panel may be distorted if fastened only with a wrench. Be sure to fix the 

elementary part with a holding wrench and fasten with a torque wrench (refer to below 

diagram). Do not apply force to the blank cap of the valve or hang a wrench, etc., on the 

cap. If blank cap is broken, it may cause leakage of refrig

erant.

Flare nut [in. (mm)]

Tightening torque [lbf·ft. (N·m)] 

1/4 (6.35) dia.

11.8 to 13.3 (16 to 18)

3/8 (9.52) dia.

23.6 to 31.0 (32 to 42)

1/2 (12.70) dia.

36.1 to 45.0 (49 to 61)

5/8 (15.88) dia.

46.5 to 55.3 (63 to 75)

3/4 (19.05) dia.

66.4 to 81.1 (90 to 110)

9374747153_IM.indb   8

2014/12/19   14:57:18

Summary of Contents for AOU36RLXFZ1

Page 1: ...Español En 1 AIR CONDITIONER OUTDOOR UNIT PART No 9374747153 INSTALLATION MANUAL For authorized personnel only MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado ...

Page 2: ...oil or equivalent used for the outdoor unit to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run NOTE Depending on the system type liquid and gas lines may be either narrow or wide Therefore to avoid confusion the refrigerant tubing for your particular...

Page 3: ...ing taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable 2 2 Special tools for R410A refrigerant Tool name Contents of change Gauge manifold Pressure is high and cannot be measured with a conventional gauge To prevent erroneous mixing of other refrigerant...

Page 4: ... 9 52 7 12 C 1 4 6 35 3 8 9 52 7 12 B 1 4 6 35 3 8 9 52 7 12 A 1 4 6 35 1 2 12 70 7 12 1 15 18 24 2 1 2 When connecting models 7 12 to the outdoor unit the included adapter is neces sary For more information refer to 4 1 3 How to use adapter Port D ø1 4 in ø3 8 in ø6 35 mm ø9 52 mm Port C ø1 4 in ø3 8 in ø6 35 mm ø9 52 mm Port B ø1 4 in ø3 8 in ø6 35 mm ø9 52 mm Port A ø1 4 in ø1 2 in ø6 35 mm ø12...

Page 5: ... unit and each indoor unit H1 49 ft 15 m Max height difference between indoor units H2 33 ft 10 m Min length for each indoor unit a b or c 16 ft 5 m Total min length a b c 49 ft 15 m 1 If the total piping is longer than 98 ft 30 m additional refrigerant charging is neces sary For more information refer to 6 2 Additional charging OUTDOOR UNIT 18 type a b H1 H1 H2 UNIT B 7 12 OUTDOOR UNIT INDOOR UNI...

Page 6: ... cable at least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you could still receive noise under some signal conditions Branch switch and circuit breaker Branch switch and circuit breaker 40 in 1 m or more 40 in 1 m or more If children under 10 years old may approa...

Page 7: ...rain as much as possible 9 Install the unit where connection to the indoor unit is easy 3 3 1 Single outdoor unit installation When the upward area is open When there are obstacles at the back side 4 in 100 m m or m ore When there are obstacles at the back and front sides AIR 4 in 100 m m or m ore 24 in 600 mm or more 3 2 Drain installation 36 type only CAUTION Perform drain work in accordance wit...

Page 8: ...g on the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space for installing the connection pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commerci...

Page 9: ...bent repeatedly at the same place it will break If pipes are shaped by hand be careful not to collapse them Do not bend the pipes at an angle of more than 90 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than 3 times 4 1 2 Pipe connection CAUTION Be sure to install the pipe against the...

Page 10: ...ning of ground fault device When the electrical switchboard is installed outdoors place it under lock and key so that it is not easily accessible Do not fasten the power supply cable and connection cable together Always keep to the maximum length of the connection cable Exceeding the maximum length may lead to erroneous operation The static electricity that is charged to the human body can damage ...

Page 11: ...ine Grounding line Power supply line Single phase 208 230 V 18 type 1 2 3 1 2 3 G G G G 1 2 3 1 L1 2 3 L2 G INDOOR UNIT OUTDOOR UNIT INDOOR UNIT A INDOOR UNIT B TERMINAL TERMINAL UNIT A UNIT B TERMINAL DISCONNECT SWITCH Locally purchased Inter unit Power lines Grounding line 208 230 V 208 230 V 208 230 V 208 230 V 208 230 V 208 230 V Power supply line Single phase 208 230 V DISCONNECT SWITCH Local...

Page 12: ...UNIT A connection cable 24 type Power supply cable UNIT C connection cable UNIT B connection cable UNIT A connection cable 18 type Power supply cable UNIT B connection cable UNIT A connection cable 5 Be sure to seal the holes when applying the putty Place the cables side by side Do not overlap the cables 6 Put the service cover and valve cover back after completion of the work ...

Page 13: ... way valve 3 Open the valve of the gauge manifold fully 4 Operate the vacuum pump and start pump down 5 Check that the compound pressure gauge reads 0 1 MPa 500 microns operate the vacuum pump for 30 minutes or more in each valve 6 At the end of pump down close the valve of the gauge manifold fully and stop the vacuum pump It checks that leave as it is for about 10 minutes and a needle does not re...

Page 14: ...setting Factory setting To set the Base heater forced off function set the DIP switch as follows 9 TEST RUN The test run method may be different for each indoor unit that is connected Refer to the installation instruction sheet included with each indoor unit CAUTION Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection 1 Indoor unit 1 Is ope...

Page 15: ... lamp and timer indicator lamp will begin to flash simultaneously during test run When using the MANUAL AUTO button of the indoor unit The remote control unit is lost and so on Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds 4 Close the valve stem...

Reviews: