3-1. FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
3-1-1 INDOOR UNIT
( Factory setting)
Setting Description
Function Number
Setting Value
Standard
(400 hours)
Long interval (1000 hours)
Short interval (200 hours)
No indication
11
00
01
02
03
1-1. Setting the Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according
to the estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function Details
1-2. Setting the Auto restart
Enable or disable automatic restart after a power interruption.
( Factory setting)
Setting Description
Function Number
Setting Value
Enable
Disable
40
00
01
Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external device.
1-3. Setting the Room temperature sensor switching
(Only for Wired remote controller)
When using the Wired remote controller temperature sensor , change the setting to “Both” (01).
( Factory setting)
Setting Description
Function Number
Setting Value
Indoor unit
Both
42
00
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
Remote controller sensor must be turned on by using the remote controller.
03-01
Summary of Contents for AOU18RLB
Page 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 24: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 71: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan December 2014 Printed in Japan ...