( Fig.1 : Outdoor temperature zone )
1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
Minimum
frequency
Maximum
frequency
Maximum
frequency
AOU09RL2
AOU12RL2
18rps
57rps
80rps
36°C
(97°F)
A zone
34°C
(93°F)
32°C
(90°F)
B zone
30°C
(86°F)
21°C
(70°F)
C zone
19°C
(66°F)
D zone
Indoor fan mode
Me
Lo
Quiet
A zone
80rps
49rps 42rps 32rps
B zone
80rps
49rps 42rps 32rps
C zone
80rps
49rps 42rps 32rps
ASU09
RL2
D zone
49rps
44rps 40rps 29rps
E zone
49rps
44rps 40rps 29rps
F zone
49rps
44rps 40rps 29rps
( Table 1 : Compressor frequency range )
01-01
E zone
F zone
10°C
(50°F)
0°C
(32°F)
12°C
(54°F)
2°C
(36°F)
* When the room temperature is between
+2°C(4°F)
to
-2.5°C(-5°F)
of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
ASU12
RL2
A zone
96rps
61rps 51rps 33rps
B zone
96rps
61rps 51rps 33rps
C zone
96rps
61rps 51rps 33rps
D zone
73rps
57rps 45rps 33rps
E zone
73rps
57rps 45rps 33rps
F zone
73rps
57rps 45rps 33rps
When the outdoor
temperature drops
When the outdoor
temperature rises
( Table 2 : Limit of maximum speed based on outdoor temperature )
80rps
96rps
Outdoor
temp. zone
Hi
* If the room temperature is
2°C(4°F)
higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency.
Summary of Contents for AOU09RL2
Page 4: ......
Page 5: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 53: ......
Page 54: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 61: ......
Page 62: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2012 Printed in Japan ...