3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
(Table 22 : Anti-freezing Protection Operation / Release Temperature)
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 67°C (152.6°F) or greater,
the compressor and the outdoor fan motor are stopped and trouble display is performed.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
01-17
Outdoor temperature
Over than 10°C
(50°F)
*1
or 12°C (53.6°F)
*2
Less than 10°C(50°F)
*1
or 12°C (53.6°F)
*2
*1. When the temperature rises.
*2. When the temperature drops.
4°C (39.2°F)
7°C (44.6°F)
13°C (55.4°F)
Temperature
Temperature
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
[ Control System ]
Indoor heat exchange
temperature rises
Indoor heat exchange
temperature drops
It returns to the normal operation
Compressor is stopped
53°C
(127.4°F)
55°C
(131°F)
63°C (145.4°F)
50°C (122°F)
The compressor frequency is
decreased 3rps every 60seconds.
The compressor frequency is
decreased 25rps every 120seconds.
Stable zone
Summary of Contents for AOU09RL2
Page 4: ......
Page 5: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 53: ......
Page 54: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 61: ......
Page 62: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2012 Printed in Japan ...