![Fujitsu AOU 9RLFW Design & Technical Manual Download Page 54](http://html.mh-extra.com/html/fujitsu/aou-9rlfw/aou-9rlfw_design-and-technical-manual_2344097054.webp)
- (02 - 20) -
OU
TDOOR
UNIT
AO
U
9
-1
5
R
L
OU
TDOOR
UNIT
AO
U
9
-1
5
R
L
ELECTRIC CHARACTERISTICS
9.
Model Name
AOU9RLFW
AOU12RLFW
AOU15RLS
Power Supply
Voltage
V
208 / 230~
Frequency
Hz
60
*1) Max. Operating Current
A
7.5
9.0
12.5
Starting Current
A
4.2
5.9
6.4
*2) Wiring Spec.
Main Fuse (Circuit breaker)
Current
A
20
Power Cable
AWG
14
*3) Limited wiring length
ft.
69
*1) The maximum current is the total current of indoor unit and outdoor unit.
*2) Wiring Spec.
Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E00005)
*3) Limited Wiring Length:
This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
Summary of Contents for AOU 9RLFW
Page 2: ...1 INDOOR UNIT WALL MOUNTED TYPE ASU9RLF ASU12RLF ASU15RLS DTR_AS044E_01 2010 08 09 ...
Page 33: ...2 OUTDOOR UNIT SINGLE TYPE AOU9RLFW AOU12RLFW AOU15RLS DTR_AO066E_01 2010 08 09 ...
Page 42: ... 02 08 OUTDOOR UNIT AOU9 15RL OUTDOOR UNIT AOU9 15RL WIRING DIAGRAMS 4 MODEL AOU9RLFW ...
Page 43: ... 02 09 OUTDOOR UNIT AOU9 15RL OUTDOOR UNIT AOU9 15RL MODEL AOU12RLFW ...
Page 44: ... 02 10 OUTDOOR UNIT AOU9 15RL OUTDOOR UNIT AOU9 15RL MODEL AOU15RLS ...
Page 53: ... 02 19 OUTDOOR UNIT AOU9 15RL OUTDOOR UNIT AOU9 15RL SOUND LEVEL CHECK POINT 8 2 39 3 8 in 1m ...