background image

En-8

TIMER OPERATION

Before using the timer function, be sure that the Remote Control Unit is set to the correct current time (

 P. 4).

To Use the ON timer or OFF timer

1

  Press the START/STOP button (Fig. 6 

R

)

 

(if the indoor unit is already operating, proceed to step 2).

 

The indoor unit’s OPERATION Indicator Lamp (green) (Fig. 3 

5

) will light.

2

  Press the TIMER MODE button (Fig. 6 

P

) to select the 

OFF timer or ON timer operation.

 

Each time the button is pressed the timer function changes in the following 
order:

 

       CANCEL  

OFF  

ON

 PROGRAM(OFF 

 ON, OFF 

 ON)

 

The indoor unit’s TIMER Indicator Lamp (orange) (Fig. 3 

6

) will light.

3

  Use the TIMER SET buttons (Fig. 6 

V

) to set the desired 

OFF time or ON time.

 

Set the time while the time display is 

fl

 ashing  (the 

fl

 ashing will continue for 

about 

fi

 ve seconds).

 button: 

Press to advance the time.

 button: 

Press to reverse the time.

 

About 

fi

 ve seconds later, the entire display will reappear.

To Use the Program timer

1

  Press the START/STOP button (Fig. 6 

R

)

 

(if the indoor unit is already operating, proceed to step 2).

 

The indoor unit’s OPERATION Indicator Lamp (green) (Fig. 3 

5

) will light.

2

  Set the desired times for OFF timer and ON timer.

 

See the section “To Use the ON timer or OFF timer” to set the desired mode 
and times.

 

About three seconds later, the entire display will reappear.

 

The indoor unit’s TIMER Indicator Lamp (orange) (Fig. 3 

6

) will light.

3

  Press the TIMER MODE button (Fig. 6 

P

) to select the 

PROGRAM timer operation (OFF   ON or OFF   ON 
will display).

 

The display will alternately show “OFF timer” and “ON timer”, then change to 
show the time setting for the operation to occur 

fi

 rst.

  The program timer will begin operation. (If the ON timer has been selected 

to operate 

fi

 rst, the indoor unit will stop operating at this point.)

 About 

fi

 ve seconds later, the entire display will reappear.

About the Program timer

  The program timer allows you to integrate OFF timer and ON timer operations in a 

single sequence. The sequence can involve one transition from OFF timer to ON timer, 
or from ON timer to OFF timer, within a twenty-four hour period.

 The 

fi

 rst timer function to operate will be the one set nearest to the current time. The 

order of operation is indicated by the arrow in the Remote Control Unit’s Display (OFF 

 ON, or OFF 

 ON).

  One example of Program timer use might be to have the air conditioner automatically 

stop (OFF timer) the operation after you go to sleep, then start (ON timer) the operation 
automatically in the morning before you arise.

To Cancel the Timer

Use the TIMER button to select “CANCEL”.
The indoor unit will return to normal 
operation.

To Change the Timer Settings

Perform steps 

2

 and 

3

.

To Stop Air Conditioner Operation while 
the Timer is Operating

Press the START/STOP button.

To Change Operating Conditions

If you wish to change operating conditions 
(Mode, Fan Speed, Thermostat Setting, 
SUPER QUIET mode), after making the timer 
setting and waiting until the entire display 
reappears, then press the appropriate buttons 
to change the operating condition desired.

To Cancel the Timer

Use the TIMER MODE button to select “CAN-
CEL”.
The air conditioner will return to normal opera-
tion.

To Change the Timer Settings

1.  Follow the instructions given in the section “To 

Use the ON Timer or OFF Timer” to select the 
timer setting you wish to change.

2.  Press the TIMER MODE button to select 

either OFF   ON or OFF   ON.

To Stop Air Conditioner Operation while 
the Timer is Operating

Press the START/STOP button.

To Change Operating Conditions

If you wish to change operating conditions 
(Mode, Fan Speed, Thermostat Setting, SUPER 
QUIET mode), after making the timer setting 
and waiting until the entire display reappears, 
then press the appropriate buttons to change 
the operating condition desired.

9317433044-05_OM.indb   8

9317433044-05_OM.indb   8

6/13/2013   2:39:54 PM

6/13/2013   2:39:54 PM

Summary of Contents for AOBR09LGC

Page 1: ...PART NO 9317433044 05 9317433044 05_OM indb 1 9317433044 05_OM indb 1 6 13 2013 2 39 16 PM 6 13 2013 2 39 16 PM ...

Page 2: ...ation stand for damage Do not place animals or plants in the direct path of the airflow Do not drink the water drained from the air conditioner Do not use in applications involving the storage of foods plants or animals precision equipment or art works Connection valves become hot during Heating handle with care Do not apply any heavy pressure to radiator fins Operate only with air filters install...

Page 3: ...ff WIRELESS REMOTE CONTROL UNIT The Wireless Remote Control Unit allows convenient control of indoor unit operation SWING OPERATION The Air Flow Direction Louvers swings automatically up and down so that the air speeds to every nook and corner of your room REMOVABLE INTAKE GRILLE The indoor unit s Intake Grille can be removed for easy cleaning and maintenance MILDEW RESISTANT FILTER The AIR FILTER...

Page 4: ...CONOMY SWING J K W L N O P V R S T U M Q Y X Fig 7 To facilitate explanation the accompanying illustra tion has been drawn to show all possible indicators in actral operation however the display will only show those indicators appropriate to the current operation NAME OF PARTS 9317433044 05_OM indb 3 9317433044 05_OM indb 3 6 13 2013 2 39 52 PM 6 13 2013 2 39 52 PM ...

Page 5: ...H Pipe Unit I Drain port bottom Fig 6 Remote Control Unit J Signal Transmitter K MODE button L 10 C HEAT button M SET TEMP button N COIL DRY button O SLEEP button P TIMER MODE button Q FAN button R START STOP button S ECONOMY button T SET button U SWING button V TIMER SET button W CLOCK ADJUST button X TEST RUN button This button is used when installing the air conditioner and should not be used u...

Page 6: ...e in the direction of the arrow while pressing the mark Batteries are not included with this product 2 Insert batteries Be sure to align the battery polarities correctly 3 Close the battery compartment lid Set the Current time 1 Press the CLOCK ADJUST button Fig 6 W Use the tip of a ball point pen or other small object to press the button 2 Use the TIMER SET buttons Fig 6 V to adjust the clock to ...

Page 7: ...e button is pressed the fan speed changes in the following order AUTO HIGH MED LOW QUIET About three seconds later the entire display will reappear When set to AUTO Heating Fan operates so as to optimally circulate warmed air However the fan will operate at very low speed when the temperature of the air issued from the indoor unit is low Cooling As the room temperature approaches that of the therm...

Page 8: ...fter which it will switch to the selected fan setting This period of time is provided to allow the indoor unit to warm up before begin full operation When the room temperature is very low frost may form on the outdoor unit and its performance may be reduced In order to remove such frost the air conditioner will automatically enter the defrost cycle from time to time Dur ing Automatic Defrosting op...

Page 9: ...t the Program timer The program timer allows you to integrate OFF timer and ON timer operations in a single sequence The sequence can involve one transition from OFF timer to ON timer or from ON timer to OFF timer within a twenty four hour period The first timer function to operate will be the one set nearest to the current time The order of operation is indicated by the arrow in the Remote Contro...

Page 10: ...ti cally raised 1 C every sixty minutes When the thermostat setting is raised a total of 2 C the thermostat setting at that time is main tained until the set time elapses at which time the air conditioner automatically turns off SLEEP timer setting During Heating operation When the SLEEP timer is set the thermostat setting is automatically lowered 1 C every thirty minutes When the ther mostat sett...

Page 11: ...g opera tion airflow will be horizontal 1 the air direction cannot be adjusted during this period Right Left Adjustment Adjust the Right Left louvers Move the Right Left louvers to adjust air flow in the direction you prefer knob two places Right Left Louvers knob ECONOMY OPERATION Begin Air Conditioner operation before performing this procedure To Use the ECONOMY Operation Press the ECONOMY butto...

Page 12: ...sappear after 10 seconds To cancel COIL DRY Operation Press the START STOP button Fig 6 R during COIL DRY Operation The indoor unit COIL DRY Indicator Lamp yellow Fig 1 7 will go out Then the opera tion stops About COIL DRY Operation Press the COIL DRY button again during COIL DRY Operation COIL DRY Operation can be reset The COIL DRY Operation cannot get rid of the existed mold or bacterium and i...

Page 13: ...emove the Intake Grille 1 Place your fingers at both lower ends of the grille panel and lift forward if the grille seems to catch partway through its movement continue lifting upward to remove 2 Pull past the intermediate catch and open the Intake Grille wide so that it become horizontal Intake Grille Mounting shaft Knob 2 Clean with water Remove dust with a vacuum cleaner wipe the indoor unit wit...

Page 14: ...ilter with the panel and push in fully making sure the two lower tabs are returned properly to their holes in the panel Hooks two places 2 Close the Intake Grille For purposes of example the illustration shows the indoor unit without Intake Grille installed Dust can be cleaned from the air filter either with a vacuum cleaner or by washing the filter in a solution of neutral deter gent and warm wat...

Page 15: ...t Mist or steam is emitted During Cooling or Dry operation a thin mist may be seen emitted from the indoor unit This results from the sudden cooling of room air by the cool air emitted from the indoor unit resulting in conden sation and misting During Heating operation water may be produced from the outdoor unit due to Automatic Defrosting operation 15 CLEANING AND CARE About the Air Cleaning Filt...

Page 16: ...ote Control Unit s setting Are the Remote Control Unit s batteries dead Are the Remote Control Unit s batteries loaded properly 5 Symptom Problem See Page NORMAL FUNCTION Airflow is weak or stops When Heating operation is started fan speed is temporarily very low to allow internal parts to warm up During Heating operation if the room temperature rises above the thermostat setting the outdoor unit ...

Page 17: ...nditioners heat your entire room by recircu lating air throughout the room with the result that some time may be required after first starting the air conditioner until the room is heated Microcomputer controlled Automatic Defrosting When using the Heating mode under conditions of low outdoor temperature and high humidity frost may form on the outdoor unit resulting in reduced operating performanc...

Page 18: ...9317433044 05_OM indb 3 9317433044 05_OM indb 3 6 13 2013 2 39 38 PM 6 13 2013 2 39 38 PM ...

Page 19: ...9317433044 05_OM indb 4 9317433044 05_OM indb 4 6 13 2013 2 39 38 PM 6 13 2013 2 39 38 PM ...

Page 20: ...9317433044 05_OM indb 2 9317433044 05_OM indb 2 6 13 2013 2 39 38 PM 6 13 2013 2 39 38 PM ...

Reviews: