5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
MODEL : AO A12L
Indoor unit
Height difference H
Connection pipe
H
Outdoor unit
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is upper than outdoor unit.
1
Indoor unit is under than outdoor unit.
2
5
7.5
10
15
20
25
15
-
-
-
0.933
0.923
0.895
10
-
-
0.980
0.933
0.923
0.895
7.5
-
1.000
0.980
0.933
0.923
0.895
5
1.026
1.000
0.980
0.933
0.923
0.895
0
1.026
1.000
0.980
0.933
0.923
0.895
-5
1.018
0.992
0.972
0.925
0.916
0.888
-7.5
-
0.988
0.968
0.922
0.912
0.885
-10
-
-
0.964
0.918
0.909
0.881
-15
-
-
-
0.903
0.894
0.867
5
7.5
10
15
20
25
15
-
-
-
0.925
0.898
0.878
10
-
-
0.999
0.934
0.907
0.887
7.5
-
0.993
1.002
0.936
0.909
0.890
5
0.949
0.995
1.005
0.939
0.912
0.892
0
0.954
1.000
1.010
0.943
0.916
0.896
-5
0.954
1.000
1.010
0.943
0.916
0.896
-7.5
-
1.000
1.010
0.943
0.916
0.896
-10
-
-
1.010
0.943
0.916
0.896
-15
-
-
-
0.943
0.916
0.896
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Pipe length (m)
Pipe length (m)
HEATING
COOLING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Height
difference H
(m)
This table is created using the maximum capacity.