SAFETY DEVICES
10.
Protection form
Model
AO
Ü
R24LC
AO
Ü
R30LC, AO
Ü
R30LF
Circuit protection
Current fuse
(NEAR THE TERMINAL)
20A 250V
20A 250V
5A 250V
5A 250V
Current fuse
(MAIN PRINTED
CIRCUIT BOARD)
15A 250V
15A 250V
3.15A 250V
3.15A 250V
Fan motor
protection
Thermal protection
program
OFF :100
+15
°C
-10
ON : 105
+15
°C
-10
OFF : 130±20°C
ON : 100±20°C
High Pressure
Protection
Pressure Switch
-
OFF : 4.2±0.1MPa
ON : 3.2±0.15MPa
Compressor
protection
Thermal protection program
(DISCHARGE TEMP.)
-
OFF : 110°C
ON : After 40 minutes
Thermal protection program
(DISCHARGE TEMP.)
OFF : 110°C
ON : After 7 minutes
OFF:110°C
ON: After 7 minutes