(5) Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few seconds until the setting value stops
flashing. If the setting value display changes or if “- -” is displayed when the flashing stops, the setting value has not been set correctly.
(An invalid setting value may have been selected for the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings. Press the SET TEMP. buttons ( ) ( ) and FAN control button simultaneously
again for more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled
after 1 minute if no operation is performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
!
CAUTION
• After turning off the power, wait 30 seconds or more before turning on it again. The Function Setting will not become active
unless the power is turned off then on again.
CONTENTS FUNCTION SETTING
• Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed
condition.
After the power is turned on, perform the Function Setting on the remote control.
• The settings may be selected between the following two: Function Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are selected.
1)
Filter sign
2)
Room temperature control for cooling
3)
Room temperature control for heating
4)
Auto restart
5)
Room temperature sensor switching
6)
Cool air prevention
7)
Remote controller custom code
8)
External input control
9)
Room temperature sensor switching (Aux.)
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
(
... Factory setting)
Setting description
Function number
Setting value
Standard (2500 hours)
11
00
Long interval (5000 hours)
01
Short interval (1250 hours)
02
No indication
03
2) Room temperature control for cooling
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
(
... Factory setting)
Setting description
Function number
Setting value
Standard
30
00
Higher control
01
Slightly lower control
02
Lower control
03