SAFETY DEVICES
10.
Protection form
Model
AO
G30LETL
AO
G36LETL
Circuit protection
Current fuse (Near the terminal)
250V 25A
Current fuse (Filter printed circuit board)
250V 10A
Current fuse (Main printed circuit board)
250V 3.15A
Fan motor protection
Thermal protection program
OFF : 140±20°C
ON : 110±20°C
High pressure protection
Pressure switch
OFF : 4.2±0.1MPa
ON : 3.2±0.15MPa
Compressor protection
Thermal protection program (Compressor temp.)
OFF : 120°C
ON : 80°C
Thermal protection program (Discharge temp.)
OFF : 110°C
ON : After 7 minutes