- (01 - 24) -
D
U
C
T T
YP
E
AR
G
30
-3
6L
M
LE
D
U
C
T T
YP
E
AR
G
30
-3
6L
M
LE
EXTERNAL INPUT & OUTPUT
11.
EXTERNAL INPUT
11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operation
Initial setting after power is ON
Starting mode other than initial setting
Operation mode
Auto changeover
Mode at previous operation
Set temperature
24°C
Temperature at previous operation
Air flow mode
AUTO
Mode at previous operation
Up-down air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Left-right air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Circuit diagram example
z
Indoor unit
control PC board
Connected unit
Ex.) Switch
Connector
1
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10m.
*10 m
Contact capacity : 24VDC or more, 10mA or more.
Please use non-polar relays and switches.
When function setting is in "Operation/Stop" mode
●
Operation
Stop
ON
OFF
Input signal
Indoor unit
When function setting is in "Forced stop" mode
●
Remote controller
ON
ON
ON
Input signal
ON
OFF
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control
operation invalidity
Parts (Optional)
z
Model name
UTD-ECS5A
Wire (External input)
Connector
INPUT
OUTPUT
REMARKS
CN102
Control input
—
See external
input/output settings for
details.
CN103
—
Operation status output
CN6
—
Fresh air control output
CN10
—
Auxiliary heater output
Summary of Contents for AO*G30LETL series
Page 2: ...1 INDOOR UNIT DTR_AR064E_01 2013 02 28 DUCT TYPE AR G30LMLE AR G36LMLE ...
Page 40: ...DTR_AO135E_01 2013 02 28 SINGLE TYPE AO G30LETL AO G36LETL 2 OUTDOOR UNIT ...
Page 46: ... 02 05 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL MODEL AO G36LETL ...
Page 51: ... 02 10 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL SOUND LEVEL CHECK POINT 88888 ...