8. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the table 9.
Cooling
Heating
Min
Max
Min
Max
Min
Max
Dry
AO*G18LFC
18rps
113rps
18rps
130rps
20rps
34rps
AO*G18LFC
40rps
59rps
72rps
85rps
101rps
110rps
(Table 9 : Compressor Operation Frequency Range)
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the fig.8.
(Fig.8 : Compressor Control at Start-up)
Time
Time
Time
Time
Time
Time
(Frequency)
(Time)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Time
Time
Time
Time
Time
Time
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
01-08
AO*G18LFC
120sec
180sec
220sec
270sec
350sec
410sec