4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 67°C or greater,
the compressor is stopped and trouble display is performed.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
01-19
[ Control System ]
Indoor heat exchange
temperature
It returns to the normal operation
Compressor is stopped
53°C
55°C
63°C
50°C
The compressor frequency is
decreased 4rps every 120seconds.
The compressor frequency is
decreased 25rps every 120seconds.
Stable zone