01-16
21.
OUTDOOR UNIT LOW NOISE OPERATION
The OUTDOOR UNIT LOW NOISE Operation functions by pressing OUTDOOR UNIT LOW NOISE button
on the remote controller.
This operation stops the PFC control, and changes the Current release operation/release value.
OUTDOOR UNIT LOW NOISE Operation mode can be used during cooling, heating and automatic operation.
It can not be used in Fan and Dry mode
Control / Release
Current release
operation/release value
3.5A / 3.0A
( Table 21 )
22. POWERFUL OPERATION
The POWERFUL OPERATION functions by pressing POWERFUL button on the remote controller.
The indoor unit & outdoor unit will operate at maximum power as shown in Table22.
Release Condition is as follows.
[Cooling / Dry]
- Room tenperature < Setting temperature - 0.5°C or Operation time has passed 20 minutes.
COMPRESSOR FREQUENCY Maximum
FAN CONT. MODE
Powerful
SETTING LOUVER
Cooling/ Dry : 3, Heating : 6
(Table22)
Powerful operation
=
=
[Heating]
- Room tenperature > Setting tempe0.5°C or Operation time has passed 20 minutes.