- (01 - 06) -
C
A
SS
ET
TE T
YP
E
AU
A3
0-
36
L
C
A
SS
ET
TE T
YP
E
AU
A3
0-
36
L
SPECIFICATIONS
3.
Type
CASSETTE MODEL
INVERTER HEATPUMP
Model name
Indoor unit
AU
A30LBLU
AU
A36LBLU
Outdoor unit
AO
A30LBTL
AO
A30LFTL
AO
A36LBTL
AO
A36LFTL
Power source
230V~ 50Hz
Available voltage range
198-264V~ 50Hz
European energy label
Cooling
A
A
Heating
A
A
Capacity
Cooling
Rated
kW
8.50
10.00
BTU/h
29000
34100
Min.-Max.
kW
2.80 - 10.00
2.80 - 11.20
BTU/h
9500 - 34100
9500 - 38200
Heating
Rated
kW
10.00
11.20
BTU/h
34100
38200
Min.-Max.
kW
2.70 - 11.20
2.70 - 12.70
BTU/h
9200 - 38200
9200 - 43300
Input power
Cooling
Rated
kW
2.65
3.11
3.12
Max.
3.88
4.56
4.22
Heating
Rated
2.77
3.02
Max.
3.88
4.56
Current
Cooling
Rated
A
11.6
13.7
*Max.
17.0
20.0
18.5
Heating
Rated
12.2
13.3
*Max.
17.0
20.0
EER
Cooling
kW/kW
3.21
3.21
COP
Heating
3.61
3.71
Moisture removal
l/h (pints/h)
2.5(5.3)
3.5(7.4)
Fan
Airflow
rate
Cooling
High
m
3
/h
1600
1800
Med
1400
1400
Low
1270
1270
Quiet
1150
1150
Heating
High
1600
1800
Med
1400
1400
Low
1270
1270
Quiet
1150
1150
Type × Q'ty
Turbo Fan × 1
Motor output
W
80
80
Sound pressure level
Cooling
High
dB(A)
40
43
Med
38
38
Low
36
36
Quiet
32
32
Heating
High
40
43
Med
38
38
Low
36
36
Quiet
32
32
Heat exchanger type
Dimensions (H × W × D)
mm
252 × 2030 × 26.6
252 × 2093 × 26.6
252 × 2030 × 26.6
252 × 2093 × 26.6
Fin pitch
1.2
1.2
Rows x Stages
2 × 12
2 × 12
Pipe type
Copper
Copper
Fin type
Aluminium
Aluminium
Enclosure (Panel)
Material
HIPS
Colour
WHITE
Approximate colour of MUNSELL N 9.25/
Dimensions
( H×W×D)
NET
Unit
mm
288 × 842 × 842
Panel
50 × 950 × 950
Gross
Unit
360 × 960 × 985
Panel
115 × 1020 × 1000
Weight
NET
Unit
kg(lb.)
26(58)
Panel
5.5(12)
Gross
Unit
32(71)
Panel
8.5(19)
Connection pipe
Size
Liquid
mm
Ø 9.52 (Ø 3 / 8 in.)
Ø 9.52 (Ø 3 / 8 in.)
Gas
Ø15.88 (Ø 5 / 8 in.)
Ø15.88 (Ø 5 / 8 in.)
Method
Flare
Flare
Operation range
Cooling
°C
18 to 32
18 to 32
%RH
80 or less
80 or less
Heating
°C
16 to 30
16 to 30
Remote controller type
WIRED
Drain pipe
Material
PVC (VP25)
Size
mm
Outer diameter : 32.0 / Inner diameter : 25.0
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
The maximum current and the maximum input value are the maximum values when operated within the operation range(temperature)
*The maximum current is the total current of indoor unit and outdoor unit.
Summary of Contents for AO*A30LBTL Series
Page 2: ...1 INDOOR UNIT D2D_AU034E 04 2010 07 07 CASSETTE TYPE AU A30LBLU AU A36LBLU ...
Page 44: ... 02 05 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A30LF AO A36LF ...
Page 46: ... 02 07 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A30LF ...
Page 47: ... 02 08 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A36LF ...
Page 54: ... 02 15 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L SOUND LEVEL CHECK POINT 88888 ...