EXTERNAL INPUT & OUTPUT
11.
Connector
INPUT
OUTPUT
REMARKS
CN102
Control input
(Operation/Stop)
—
See external
input/output settings for
details.
CN103
—
Operation status output
CN6
—
Fresh air control output
EXTERNAL INPUT
11-1.
CONTROL INPUT (Operation/Stop)
The air conditioner can be remotely operated by means of the following on-site work.
Operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Initial starting after power turned on
Starting other than at the left
Operation mode
Auto changeover
Mode at previous operation
Set temperature
24°C
Temperature at previous operation
Air flow mode
AUTO
Mode at previous operation
Up-down air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Left-right air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Circuit diagram example
z
Indoor
control PC board
Connected unit
Ex.) Switch
Connector
1
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10m.
Contact capacity : 12VDC or more, 15mA or more.
Please use the non-polar relays and switches.
*10 m
Operation
Stop
ON
OFF
Input signal
Indoor unit
Parts (Optional)
z
Model name
UTY-XWZX
Wire (External input)
Summary of Contents for AO*A30LBTL Series
Page 2: ...1 INDOOR UNIT D2D_AU034E 04 2010 07 07 CASSETTE TYPE AU A30LBLU AU A36LBLU ...
Page 44: ... 02 05 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A30LF AO A36LF ...
Page 46: ... 02 07 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A30LF ...
Page 47: ... 02 08 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A36LF ...
Page 54: ... 02 15 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L SOUND LEVEL CHECK POINT 88888 ...