background image

En-2

MANUAL AUTO OPERATION

Use the MANUAL AUTO operation in the event the remote control unit is 
lost or otherwise unavailable.
*Limited to only when receiver unit is connected.

 CAUTION

Do not press the MANUAL AUTO button with wet hands or pointed objects, 
otherwise an electric shock or malfunction may occur.

Starting Operation

Press the MANUAL AUTO button on the operating con-
trol panel.

The operation can be set in the following setting.

Operating mode

AUTO:
When Auto mode cannot be selected, it will oper-
ate in the same mode as the other indoor unit in 
the same system. (When other indoor unit in the 
same system doesn’t operate, the air conditioner 
will operate in cooling.)

Fan speed

AUTO

Setting temperature

74°F (23 °C)

Stopping Operation

Press the MANUAL AUTO button on the operating con-
trol panel.

OPERATING TIPS

Operation and Performance

About priority state and standby state

 

Multiple indoor units can be connected within the same system. Depend-
ing on the system, choice of operating mode are limited.

Cooling priority 
state

When the other indoor units within the same system 
operate in cooling or dry mode, heating can not be 
selected at the same time.

Heating priority 
state

When the other indoor units within the same system 
operate in heating mode, cooling and dry mode can not 
be selected at the same time.

Standby state

The standby state activates when 2 or more indoor 
units start up at the same time in different mode. Any 
indoor unit other than priority mode will wait in standby 
state until priority mode changes (operation starts as 
soon as priority is switched).
At this time, the OPERATION indicator lamp (green) 
lights up and the TIMER indicator lamp (orange) 

fl

 ash-

es. (limited to only when receiver unit is connected)

Low ambient cooling

 

When the outdoor temperature drops, the outdoor unit’s fans may switch 
to Low Speed, or one of the fans may stop intermittently.

Heating performance

 

Heating mode operates on the heat-pump principle, absorbing heat from 
outdoor air and transferring that heat indoors. As a result, the operating 
performance is reduced as outdoor air temperature drops. If you feel that 
insuf

fi

 cient heating performance is being produced, we recommend you 

use this air conditioner in conjunction with another type of heating appli-
ance.

 

Heating mode heat your entire room by recirculating air throughout the 
room, with the result that some time may be required after 

fi

 rst starting 

the air conditioner until the room is heated.

Microcomputer-controlled automatic defrosting

 

When using the Heating mode under conditions of low outdoor air tem-
perature high humidity, frost may form on the outdoor unit, resulting in 
reduced operating performance. In order to prevent this kind of reduced 
performance, this unit is equipped with a Microcomputer-controlled auto-
matic defrosting function. If frost forms, the air conditioner will temporar-
ily stop, and the defrosting circuit will operate brie

fl

 y (for about 4 to 15 

minutes). 
During Automatic Defrosting operation, the OPERATION indicator lamp 
(green) will 

fl

 ash (limited to only when receiver unit is connected).

Oil recovery operation 

 

Periodically, the oil recovery operation is performed in order to return 
compressor oil to the outdoor unit. 
During oil recovery operation, the OPERATION indicator lamp (green) will 

fl

 ash (for about 10 minutes) (limited to only when receiver unit is con-

nected).

Temperature and humidity range

 

The temperature and humidity required for operating this product is as 
shown in the following table.

Cooling/Dry Mode

Heating Mode

Outdoor 
temperature

Please refer to the speci

fi

 cation of outdoor units.

Indoor 
temperature

About 64 to 90 °F DB

(18 to 32 °C DB)

About 50 to 86 °F DB

(10 to 30 °C DB)

Indoor humidity

About 80% or less

 

If the air conditioner is operated under higher temperature conditions than 
those listed, the built-in protection circuit may operate to prevent internal 
circuit damage. Also, during Cooling and Dry modes, if the unit is used 
under conditions of lower temperature than those listed above, the heat-
exchanger may freeze, leading to water leakage and other damage.

 

If the unit is used for long periods under high-humidity conditions, con-
densation may form on the surface of the indoor unit, and drip onto the 

fl

 oor or other objects underneath.

 

Do not use this unit for any purposes other than the Cooling, Heating, 
Dehumidifying, and air-circulation of rooms in ordinary dwellings.

Summary of Contents for Airstage VR-II ARUV12TLAV

Page 1: ...TING MANUAL INDOOR UNIT Duct type Keep this manual for future reference MODE D EMPLOI UNITÉ INTÉRIEURE type conduit Conservez ce manuel pour pour toute référence ultérieure MANUAL DE FUNCIONAMIENTO UNIDAD INTERIOR Tipo conducto Conserve este manual para posibles consultas futuras English Français Español ...

Page 2: ...ioner or the air filter Do not pour water or cleaning solvent on the unit directly or wash the unit with them Do not expose the air conditioner directly to water Do not operate the air conditioner with wet hands Check the condition of the installation stand for damage Operate only with air filters installed Do not drink the water drained from the air conditioner Do not apply any heavy pressure to ...

Page 3: ...e drops If you feel that insufficient heating performance is being produced we recommend you use this air conditioner in conjunction with another type of heating appli ance Heating mode heat your entire room by recirculating air throughout the room with the result that some time may be required after first starting the air conditioner until the room is heated Microcomputer controlled automatic def...

Page 4: ...erates See page 2 The fan may operate at low speed during Dry operation or when the unit is monitoring the room s temperature In the monitor AUTO operation the fan will operate at low speed Flashing lamps Limited to only when receiver unit is connected The OPERATION indicator lamp green flashes An oil recovery operation is being performed See page 2 The OPERATION indicator lamp green flashes An au...

Page 5: ...TER indicator lamp red is flashing very fast when receiver unit is connected The wired remote controller or simple remote controller indicate Er when connected It has burning smell For details on marking the Flashing lamps please refer to the Manual of IR Receiver Unit or Wired Remote Controller SPECIFICATIONS MODEL ARUV12 TLAV ARUV18 TLAV ARUV24 TLAV POWER SOURCE 208 230 V 60 Hz AVAILABLE VOLTAGE...

Page 6: ......