background image

En-2

2.3. Accessories

Do not discard the accessories required for installation until the installation work is 
complete.

Name and shape

Q’ty

Application

Installation Manual

1

This manual

Hanger

3

For suspending the RB unit from 
ceiling

Washer

6

For suspending the RB unit from 
ceiling

Tapping screw A
(

Φ

4×10)

6

For suspending the RB unit from 
ceiling

Tapping screw B
(

Φ

4×25)

4

For suspending the RB unit from 
wall

Cable tie

2

For mounting the transmission 
cable

Cable clamp

1

For mounting the cable

Reducer type

UTP-

RX01AH

UTP-

RX01BH

UTP-

RX01CH

Reducer-A

a

b

a: ø9.52 [O.D.] b: ø12.7 [I.D.]

4

Reducer-B

a

b

a: ø12.7 [O.D.] b: ø15.88 [I.D.]

2

1

Reducer-C

a

b

a: ø12.7 [O.D.] b: ø9.52 [I.D.]

1

Reducer-D

a

b

a: ø19.05 [O.D.] b: ø22.22 [I.D.]

2

Reducer-E

a

b

с

a: ø19.05 [O.D.] b: ø12.7 [I.D.]
c: ø15.88 [I.D.]

2

Reducer-F

a

b

a: ø19.05 [O.D.] b: ø15.88 [I.D.]

1

2.4.  Optional parts

The following optional parts are available.

Description

Model No.

Application

External connect kit

UTY-XWZXZ6

For external input
(Dry contact terminal / CNA01)

UTY-XWZXZB

For external input
(Apply voltage terminal / CNA02)

3. PRODUCT SELECTION

 

Select the RB unit to 

fi

 t the total capacity and number of the indoor units to be con-

nected downstream. (Refer to Tables 1 and 2)

I.U.=Indoor unit
RB=RB unit
O.U.=Outdoor unit

O.U.

RB

I.U.

I.U.

Calculation example: If the connected indoor units model code is 07, 09, 12 and 18.
 

Q1 = 2.2kW + 2.8kW + 3.6kW + 5.6kW = 14.2kW

 

   Select “UTP-RX01BH”

Table 1) Conditions in which connection is possible

Model Name

Indoor unit capacity

Maximum number of con-

nectable indoor units

UTP-RX01AH

2.2 

 Q1 

 8.0kW

Up to 3 units

UTP-RX01BH

2.2 

 Q1 

 18.0kW

Up to 8 units

UTP-RX01CH

2.2 

 Q1 

 28.0kW

Up to 8 units

* Indoor units connected downstream of the RB unit can operate all in the same operat-

ing mode. Indoor units within the same RB group cannot simultaneously operate heat-
ing and cooling.

Table 2) Indoor unit model codes and model selection capacity

Model code

07

09

12

14

18

24

30

36

Indoor unit

capacity (Kw)

2.2

2.8

3.6

4.0
4.5

5.6

7.1

8.0
9.0

11.2

Model code

45

54

60

72

90

Indoor unit

capacity (Kw)

12.5

14.0

18.0

22.4

25.0

 

For connectable indoor units, refer to the catalogue or the Design & Technical manual.

4.  PIPING SPECIFICATIONS

For details of piping speci

fi

 cations, refer to the outdoor unit installation manual.

5. INSTALLATION WORK

5.1.  Selecting an installation location

 WARNING

Take into consideration whether the place you install the main unit can fully with-
stand its weight.
For hanger bolts, use embedded inserts or embedded foundation bolts in the case 
of new installation, and use a hole-in-anchor if already installed, and attach in a 
way so that the unit’s weight can be supported.

 CAUTION

Do not install this unit in the following areas:
•  Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

• Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, 

such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit 
to leak water.

•  Area that generates substances that adversely affect the equipment, such as sulfu-

ric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints 
to corrode, which can cause refrigerant leakage.

•  Area containing equipment that generates electromagnetic interference. It will cause 

the control system to malfunction, preventing the unit from operating normally.

•  Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable dust, or volatile in

fl

 ammables such as paint thinner or gasoline. If gas 

leaks and settles around the unit, it can cause a 

fi

 re.

•  Area where small animals may live. It may cause failure, smoke or 

fi

 re if small 

animals enter and touch internal electrical parts.

•  Area where animals may urinate on the unit or ammonia may be generated.

Install this unit, power supply cable and transmission cable at least 1 m away 
from a television or radio receivers. The purpose of this is to prevent TV reception 
interference or radio noise. (Even if they are installed more than 1 m apart, you 
could still receive noise under some signal conditions.)

If children under 10 years old may approach the unit, take preventive measures so 
that they cannot reach the unit.

9366249047-03_IM.indb   Sec1:2

9366249047-03_IM.indb   Sec1:2

2015/3/10   14:27:45

2015/3/10   14:27:45

Summary of Contents for Airstage UTP-RX01AH

Page 1: ...NSTALLAZIONE UNITÀ REFRIGERANTE SECONDARIA A uso esclusivo del personale tecnico autorizzato Ελληνικά Português ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΜΟΝΆΔΑ ΔΙΑΚΛΆΔΩΣΗΣ ΨΥΚΤΙΚΟΎ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE DE DERIVAÇÃO DE REFRIGERANTE Apenas para técnicos autorizados Русский Türkçe РУКОВОДСТВО ПО УСТАНОВКЕ МОДУЛЬ ВЕТКИ ОХЛАЖДЕНИЯ Только для авторизованного обслуживающ...

Page 2: ...rectly grounded and the supply line must be equipped with a dif ferential breaker in order to protect the persons The units are not explosion proof and therefore should not be installed in explosive atmosphere Do not turn on the power until all installation work is complete This unit contains no user serviceable parts Always consult authorized service per sonnel to repairs When moving consult auth...

Page 3: ...or connectable indoor units refer to the catalogue or the Design Technical manual 4 PIPING SPECIFICATIONS For details of piping specifications refer to the outdoor unit installation manual 5 INSTALLATION WORK 5 1 Selecting an installation location WARNING Take into consideration whether the place you install the main unit can fully with stand its weight For hanger bolts use embedded inserts or emb...

Page 4: ...33 18 22 147 172 298 147 89 Unit mm Top side A B C 198 155 124 206 48 75 198 268 30 Indoor unit side Outdoor unit side 400 400 100 Unit mm service access Service access A C B Outdoor unit side 500 or more 500 or more 20 or more 20 or more Ceiling hanging Installation limit Unit mm 5 2 2 Wall hanging 333 18 15 198 268 198 7 Unit mm service space grille 20 or more Installation limit 20 or more 300 o...

Page 5: ... Control box Control box cover Cable clamp 6 Change the control box attachment position 7 Attach the cable clamp ac cessory Thereafter put the cable in the cable clamp 8 Fix the control box position 4 screws 9 Attach Cover B to Cover A 1 screw 10 Attach Cover A 4 screws 11 Attach the control box cover 2 screws 5 7 Installation of the unit WARNING Perform installation in a location which can proper...

Page 6: ... ø12 7 1 2 Reducer 5 6 7 1 8 0 9 0 ø15 88 5 8 Reducer ø12 7 1 2 ø15 88 5 8 Reducer 11 2 12 5 14 0 ø19 05 3 4 ø12 7 1 2 ø19 05 3 4 18 0 ø19 05 3 4 ø15 88 5 8 Reducer ø19 05 3 4 Table 3 Connection pipe selection for when 2 to 8 indoor units are connected Total capacity of indoor unit kW Suction gas pipe mm in Discharge gas pipe mm in Gas pipe mm in 4 4 to 11 1 ø15 88 5 8 Reducer ø12 7 1 2 ø15 88 5 8...

Page 7: ...n Locally purchased Cable tie Locally purchased RB Unit 7 ELECTRICAL WIRING 7 1 Safety precautions for electrical wiring WARNING Electrical work must be performed in accordance with this Manual by a person certified under the national or regional regulations Be sure to use a dedicated circuit for the unit An insufficient power supply circuit or improperly performed electrical work can cause seriou...

Page 8: ...ly and transmission cable Recommended cable size mm2 Cable type Remark Power supply cable 2 5 Type60245 IEC57 or equivalent 1ø 50 Hz 198 to 264 V 2 Cable earth ground Transmission cable 0 33 LONWORKS compatible cable 22 AWG LEVEL 4 NEMA non polar 2 core twisted pair solid core diameter 0 65 mm 7 3 Wiring 7 3 1 Power supply cable Keep the ground cable longer than the other cables 20 mm Power supply...

Page 9: ...cable cannot be used to connect indoor units belonging to different RB groups GOOD PROHIBITED Refrigerant pipe RB group 1 RB group 1 RB group 2 RB group 2 Transmission line Transmission line L N L N L N L N L N L N Crossover wiring of power supply RB unit RB unit Pull box Power supply Power supply Power supply Breaker Power supply 230V 1ø 50Hz RB unit RB unit Power supply GOOD PROHIBITED Transmiss...

Page 10: ...ddress Manual address setting Setting example 2 RB AD 10 RB AD 1 Automatic address setting Set this switch to 00 at factory setting 0 to 63 Refrigerant circuit address Manual address setting Setting example 63 REF AD 10 REF AD 1 Automatic address setting Set this switch to 00 at factory setting 0 to 99 For details of automatic address setting please refer to the outdoor unit installation manual 8 ...

Page 11: ...OOLING HEATING PRIORITY FUNCTION Edge input only Connector Input signal Command CNA01 or CNA02 OFF ON Heating priority ON OFF Cooling priority CNA01 or CNA02 Priority mode Heating On Off Cooling 10 TEST RUN 10 1 Test run using Outdoor unit PC board Refer to the Installation Manual for the outdoor unit to perform the test run using the outdoor unit 10 2 Test run using Remote Controller Refer to the...