background image

En-4

SPECIFICATIONS

MODEL

ARXK

007

GLFH

ARXK

009

GLFH

ARXK

012

GLFH

ARXK

014

GLFH

ARXK

018

GLFH

ARXK

024

GLFH

POWER SOURCE

230 V ~ 50/60 Hz

AVAILABLE VOLTAGE 
RANGE 

198 to 264V (50Hz)
198 to 253V (60Hz)

COOLING 
CAPACITY

[kW]

2.2

2.8

3.6

4.5

5.6

7.1

[Btu/h] 7,500

9,600

12,300 15,400 19,100 24,200

HEATING 
CAPACITY

[kW]

2.8

3.2

4.0 5.0 6.3

8.0 

[Btu/h] 9,600

10,900 13,600 17,100 21,500 27,300

INPUT POWER

[W]

21

21

28

59

66

73

CURRENT

[A]

0.22

0.22

0.29

0.53

0.54

0.60

SOUND PRESSURE LEVEL

HIGH

dB [A]

26

26

29

34

33

32

MED - HIGH dB [A]

25

25

27

31

30

30

MED

dB [A]

24

24

26

28

28

28

MED - LOW

dB [A]

23

23

25

26

26

27

LOW

dB [A]

22

22

24

24

24

25

QUIET

dB [A]

21

21

22

22

22

22

DIMENSIONS & WEIGHT 

HEIGHT

[mm]

198

198

198

WIDTH

[mm]

700

900

1,100

DEPTH

[mm]

450

450

450

WEIGHT

[kg]

15.0 15.5 

18.5 

22.0 

MODEL

ARXK

004

GLEH

ARXK

007

GLEH

ARXK

009

GLEH

ARXK

012

GLEH

ARXK

014

GLEH

ARXK

018

GLEH

ARXK

024

GLEH

POWER SOURCE

230 V ~ 50/60 Hz

AVAILABLE VOLT-
AGE RANGE 

198 to 264V (50Hz)
198 to 253V (60Hz)

COOLING 
CAPACITY

[kW]

1.1

2.2

2.8

3.6

4.5

5.6

7.1

[Btu/h] 3,800 7,500 9,600 12,300 15,400 19,100 24,200

HEATING 
CAPACITY

[kW]

1.3

2.8

3.2

4.0 5.0 6.3

8.0 

[Btu/h] 4,400 9,600 10,900 13,600 17,100 21,500 27,300

INPUT 
POWER

[W]

26

28

28

35

66

73

80

CURRENT

[A] 0.21

0.23

0.23

0.30

0.54

0.55

0.61

SOUND PRESSURE LEVEL

HIGH

dB [A]

25

26

26

29

34

33

32

MED - 
HIGH

dB [A]

24

25

25

27

31

30

30

MED

dB [A]

23

24

24

26

28

28

28

MED - 
LOW

dB [A]

22

23

23

25

26

26

27

LOW

dB [A]

21

22

22

24

24

24

25

QUIET

dB [A]

20

21

21

22

22

22

22

DIMENSIONS & WEIGHT

HEIGHT

[mm]

198

198

198

WIDTH

[mm]

700

900

1,100

DEPTH

[mm]

450

450

450

WEIGHT

[kg] 14.5

15.5 16.0 

19.0 22.5 

 

Acoustic Noise Information :
The maximum sound pressure level is less than 70 dB (A) for both 
indoor unit and outdoor unit. According to IEC 704-1 and ISO 3744.

 

Standard static pressure :  10 Pa  (AR004/007/009/012)   

15 Pa  (AR014/018/024) 

9381857104_OM_9L.indb   4

9381857104_OM_9L.indb   4

2019/1/29   11:02:32

2019/1/29   11:02:32

Summary of Contents for AIRSTAGE ARXK007GLFH

Page 1: ... ISTRUZIONI UNITÀ INTERNA tipo a condotto Conservare questo manuale per consultazione futura ΕΓΧΕΙΡΙΔΙΟ ΛΕΙΤΟΥΡΓΙΑΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύπος αγωγού Διατηρήστε το παρόν εγχειρίδιο για μελλοντική αναφορά РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ ВНУТРЕННИЙ МОДУЛЬ Короб Сохраните данное руководство для последующего использования KULLANIM KILAVUZU İÇ ÜNİTE Kanal tipi Bu kılavuzu ileride başvurmak üzere saklayın Origi...

Page 2: ... wash the unit with them Do not expose the air conditioner directly to water Do not operate the air conditioner with wet hands Check the condition of the installation stand for damage Operate only with air filters installed Do not drink the water drained from the air conditioner Do not apply any heavy pressure to radiator fins Do not use inflammable gases near the air conditioner Do not touch the ...

Page 3: ...icient heating performance is being produced we recommend you use this air conditioner in conjunction with another type of heating appliance Heating mode heat your entire room by recirculating air throughout the room with the result that some time may be required after first starting the air conditioner until the room is heated Microcomputer controlled automatic defrosting When using the Heating m...

Page 4: ...s the standby state See page 2 Noise is heard In the following conditions there are sounds of water flowing from the indoor unit and the operation sound becomes loud These are the sounds of the flowing of refrigerant When operation starts When oil recovery operation finishes When automatic defrosting operation finishes During operation a slight squeaking sound may be heard This is the result of mi...

Page 5: ...RXK 018 GLEH ARXK 024 GLEH POWER SOURCE 230 V 50 60 Hz AVAILABLE VOLT AGE RANGE 198 to 264V 50Hz 198 to 253V 60Hz COOLING CAPACITY kW 1 1 2 2 2 8 3 6 4 5 5 6 7 1 Btu h 3 800 7 500 9 600 12 300 15 400 19 100 24 200 HEATING CAPACITY kW 1 3 2 8 3 2 4 0 5 0 6 3 8 0 Btu h 4 400 9 600 10 900 13 600 17 100 21 500 27 300 INPUT POWER W 26 28 28 35 66 73 80 CURRENT A 0 21 0 23 0 23 0 30 0 54 0 55 0 61 SOUND...

Page 6: ...9381857104_OM_9L indb 6 9381857104_OM_9L indb 6 2019 1 29 11 02 35 2019 1 29 11 02 35 ...

Reviews: