background image

En-3

CLEANING AND CARE

 CAUTION

 

Before cleaning the unit, be sure to stop the unit and disconnect the 
power supply.

 

Do not stand on an unstable platform when cleaning.

 

When removing and replacing the air 

fi

 lters, be sure not to touch the 

heat exchanger, as personal injury may result.

 

Do not clean the inside of the unit by yourself. To clean the inside, 
always consult authorized service personnel.

 

When cleaning the unit’s body, do not use water hotter than 40 °C, 
harsh abrasive cleansers, or volatile agents like benzene or thinner.

 

If dirt is allowed to accumulate on the air 

fi

 lter, air

fl

 ow will be reduced, 

lowering operating ef

fi

 ciency and increasing noise. 

During periods of normal use, the air 

fi

 lter should be cleaned every 2 

weeks.

Cleaning the air 

fi

 lter

Cleaning

Cleaning the air 

fi

 lter

Remove dust with a vacuum cleaner or by washing. After washing, be 
sure to allow it to dry thoroughly in a shady place before reinstalling.

When not using for an extended period

Leave the breaker on for at least 12 hours before starting operation 
when it is to be used again.

TROUBLESHOOTING

The following conditions are not breakdowns or op-
eration failures.

Doesn’t operate immediately:

 

If the unit is stopped and then immediately started again, the com-
pressor will not operate for about 3 minutes, in order to prevent fuse 
blowouts.

 

Whenever the electrical breaker is turned off then on again, the protec-
tion circuit will operate for about 3 minutes, preventing unit operation 
during that period.

Air

fl

 ow is weak or stops:

 

When Heating operation is started, indoor unit’s fan may temporarily 
stop, to allow internal parts to warm up.

 

During Heating operation, if the room temperature rises above the 
thermostat setting, the outdoor unit will stop, and the indoor unit’s fan 
will stop. If you wish to warm the room further, set the thermostat for a 
higher setting.

 

During oil recovery operation, the air

fl

 ow may stop for approximately 

10 minutes. (See page 2)

 

During Heating operation, the unit will temporarily stop operation (be-
tween 4 and 15 minutes) as the Automatic Defrosting mode operates. 
(See page 2)

 

The fan may operate at low speed during Dry operation or when the 
unit is monitoring the room’s temperature.

 

In the monitor AUTO operation, the fan will operate at low speed.

Flashing lamps:
(Limited to only when receiver unit is connected)

 

The Operation indicator lamp (green) 

fl

 ashes:

An oil recovery operation is being performed. (See page 2)

 

The Operation indicator lamp (green) 

fl

 ashes:

An automatic defrosting operation is being performed. (See page 2)

 

The Operation indicator lamp (green) and Timer indicator lamp (or-
ange) are 

fl

 ashing alternately:

It has recovered from a power outage.

 

The Operation indicator lamp (green) and Timer indicator lamp (or-
ange) are 

fl

 ashing simultaneously:

It is operating in trial operation mode. Ask a manager as there may be 
maintenance being conducted.

 

The Operation indicator lamp (green) lights up and the Timer indicator 
lamp (orange) 

fl

 ashes:

This is the standby state. (See page 2)

Noise is heard:

 

In the following conditions there are sounds of water 

fl

 owing from the 

indoor unit and the operation sound becomes loud. These are the 
sounds of the 

fl

 owing of refrigerant.

 When operation starts 
When oil recovery operation 

fi

 nishes 

When automatic defrosting operation 

fi

 nishes

 

During operation, a slight squeaking sound may be heard. This is the 
result of minute expansion and contraction of the panel due to tem-
perature changes.

 

During Heating operation, a sizzling sound may be heard occasionally. 
This sound is produced by the Automatic Defrosting operation. (See 
page 2)

Smells:

 

Some smell may be emitted from the indoor unit. This smell is the 
result of room smells (furniture, tobacco, etc.) which have been taken 
into the air conditioner.

Fog comes out of the indoor unit:

 

During Cooling operation, a thin mist may be seen emitted from the 
indoor unit. This results from the sudden Cooling of room air by the air 
emitted from the air conditioner, resulting in condensation and misting.

Steam comes out of the indoor unit:

 

During Heating operation, the outdoor unit’s fan may stop, and steam 
may be seen rising from the unit. This is due to the Automatic Defrost-
ing operation. (See page 2)

Water is produced from the outdoor unit:

 

During Heating operation, water may be produced from the outdoor 
unit due to the Automatic Defrosting operation.

The following conditions may not be breakdowns so 
check again.

Doesn’t operate at all:

 

Has there been a power failure?

 

Has a fuse blown out, or a circuit breaker been tripped?

 

Is the main power switch set to the OFF position?

 

Are you trying to engage in an operation different from the priority 
state? (See page 2)

 

Is it in standby state? (See page 2)

The operation mode cannot be changed:

 

Are you trying to change to an operation different from the priority 
conditions? (See page 2)

Poor Cooling (or Heating) performance:

 

Did you adjust the room temperature settings (thermostat) correctly?

 

Is the air 

fi

 lter dirty? (See page 3)

 

Are the air conditioner’s inlet port or outlet port blocked?

 

Is there a window or door open?

 

In the case of Cooling operation, is a window allowing bright sunlight to 
enter? (Close the curtains.)

 

In the case of Cooling operation, are there heating apparatus and com-
puters inside the room, or are there too many people in the room?

 

Is the fan speed set to low?

Set the temperature lower than the room temperature and use it:

 

Temperature does not fall down well. Temperature may not fall down 
depending on the room conditions. (While high humidity or the room 
temperature is high.) (See page 2)

In the following situations stop operation immediately 
and get in touch with authorized service personnel.

 

The problem cannot be solved even when the troubleshooting checks 
have been performed.

 

The FILTER indicator lamp (red) is 

fl

 ashing very fast (when receiver 

unit is connected).

 

The wired remote controller or simple remote controller indicate Er 
(when connected).

 

It has burning smell.

 

For details on marking the Flashing lamps, please refer to the Manual 
of “IR Receiver Unit” or “Wired Remote Controller”.

9381857104_OM_9L.indb   3

9381857104_OM_9L.indb   3

2019/1/29   11:02:32

2019/1/29   11:02:32

Summary of Contents for AIRSTAGE ARXK007GLFH

Page 1: ... ISTRUZIONI UNITÀ INTERNA tipo a condotto Conservare questo manuale per consultazione futura ΕΓΧΕΙΡΙΔΙΟ ΛΕΙΤΟΥΡΓΙΑΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύπος αγωγού Διατηρήστε το παρόν εγχειρίδιο για μελλοντική αναφορά РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ ВНУТРЕННИЙ МОДУЛЬ Короб Сохраните данное руководство для последующего использования KULLANIM KILAVUZU İÇ ÜNİTE Kanal tipi Bu kılavuzu ileride başvurmak üzere saklayın Origi...

Page 2: ... wash the unit with them Do not expose the air conditioner directly to water Do not operate the air conditioner with wet hands Check the condition of the installation stand for damage Operate only with air filters installed Do not drink the water drained from the air conditioner Do not apply any heavy pressure to radiator fins Do not use inflammable gases near the air conditioner Do not touch the ...

Page 3: ...icient heating performance is being produced we recommend you use this air conditioner in conjunction with another type of heating appliance Heating mode heat your entire room by recirculating air throughout the room with the result that some time may be required after first starting the air conditioner until the room is heated Microcomputer controlled automatic defrosting When using the Heating m...

Page 4: ...s the standby state See page 2 Noise is heard In the following conditions there are sounds of water flowing from the indoor unit and the operation sound becomes loud These are the sounds of the flowing of refrigerant When operation starts When oil recovery operation finishes When automatic defrosting operation finishes During operation a slight squeaking sound may be heard This is the result of mi...

Page 5: ...RXK 018 GLEH ARXK 024 GLEH POWER SOURCE 230 V 50 60 Hz AVAILABLE VOLT AGE RANGE 198 to 264V 50Hz 198 to 253V 60Hz COOLING CAPACITY kW 1 1 2 2 2 8 3 6 4 5 5 6 7 1 Btu h 3 800 7 500 9 600 12 300 15 400 19 100 24 200 HEATING CAPACITY kW 1 3 2 8 3 2 4 0 5 0 6 3 8 0 Btu h 4 400 9 600 10 900 13 600 17 100 21 500 27 300 INPUT POWER W 26 28 28 35 66 73 80 CURRENT A 0 21 0 23 0 23 0 30 0 54 0 55 0 61 SOUND...

Page 6: ...9381857104_OM_9L indb 6 9381857104_OM_9L indb 6 2019 1 29 11 02 35 2019 1 29 11 02 35 ...

Reviews: