En-17
8. TEST RUN
8.1. Test run using Outdoor unit (PCB)
•
Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
8.2. Test run using Remote Controller
•
Refer to the Installation Manual for the remote controller to perform the test run using the
wireless remote controller.
•
When the air conditioner is being test run, the OPERATION and TIMER indicators flash
slowly at the same time.
9. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
CHECK ITEMS
If not performed correctly
CHECK
BOX
Has the indoor unit been installed cor-
rectly?
Vibration, noise, indoor unit
may drop
Has there been a check for gas leaks
(refrigerant pipes)?
No cooling, No heating
Has heat insulation work been completed? Water leakage
Does water drain easily from the indoor
units?
Water leakage
Is the voltage of the power source the
same as that indicated on the label on the
indoor unit?
No operation, heat or burn
damage
Are the wires and pipes all connected
completely?
No operation, heat or burn
damage
Is the indoor unit earthed (grounded)?
Short circuit
Is the connection cable the specified
thickness?
No operation, heat or burn
damage
Are the inlets and outlets free of any
obstacles?
No cooling, No heating
Does start and stop air conditioner op-
eration by remote control unit or external
device?
No operation
After installation is completed, has the
proper operation and handling been
explained to the user?
10. ERROR CODES
If you use a wired type remote controller, error codes will appear on the remote controller
display. If you use a wireless remote controller, the lamp on the photodetector unit will
output error codes by way of blinking patterns. See the lamp blinking patterns and error
codes in the table below.
Error indications
Wired remote
controller
error code
Error contents
OPERATION
lamp (green)
TIMER lamp
(orange)
FILTER lamp
(red)
(1)
(2)
Remote controller communi-
cation error
(1)
(4)
Network communication error
(1)
(6)
Peripheral unit communica-
tion error
(2)
(6)
Indoor unit address setting
error
(2)
(9)
Connection unit number error
in wired remote controller
system
(3)
(1)
Indoor unit power supply
abnormal
(3)
(2)
Indoor unit main PCB error
(3)
(10)
Indoor unit communication
circuit (wired remote control-
ler) error
(4)
(1)
Indoor unit room temp. therm-
istor error
(4)
(2)
Indoor unit heat ex. temp.
thermistor error
(5)
(1)
Indoor unit fan motor 1 error
(5)
(2)
Indoor unit coil (expansion
valve) error
(5)
(3)
Indoor unit water drain
abnormal
(9)
(15)
Outdoor unit miscellaneous
error
(10)
(8)
Poor refrigerant circulation
(13)
(1)
RB unit error
Display mode
: 0.5 s ON / 0.5 s OFF
: 0.1 s ON / 0.1 s OFF
( ) : Number of flashing
Wired remote controller display
UTY-RNRUZ* (2-wire type)
Status
Air Flow Direction
VT
Off
1
3
Off
HZ
Economy
Individual
Anti Freeze
Page 1/ 4
Monitor
Next
Page
Error
Information
Set Temp.
Mode
Menu
Status
Fan
Fri 10:00AM
Unoccupied
Error icon
Touch the [Status].
Touch the [Error Information].
2-digit numbers are corresponding to
the error code in the preceding table.
Touch the [Next Page] (or [previous page])
to switch to other indoor unit information.
For more information, refer to the installation manual of the remote controller.
For details on marking the ERROR CODES, please refer to the Manual of “IR Receiver
Unit” or “Wired Remote Controller”.