En-9
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again.
The Function Setting does not become active unless the power is turned off then on
again.
Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the fi lter. Select the
time setting for the fi lter sign display interval in the table below according to the amount
of dust or debris in the room. If you do not wish the fi lter sign to be displayed, select the
setting value for “No indication”.
(
♦
... Factory setting)
Setting Description
Function Number
Setting Value
Standard (400 hours)
11
00
Long interval (1,000 hours)
01
Short interval (200 hours)
02
♦
No indication
03
Setting vane
When embedding the indoor unit in a wall, restrict the movement of the horizontal vane for
the upper air outlet so that it only operates horizontally.
If this setting is not performed, heat will build up in the wall and the room will not be cooled
or warmed properly.
(
♦
... Factory setting)
Setting Description
Function Number
Setting Value
♦
Standard
23
00
(Setting forbidden)
01
In a wall
02
Cooling Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be selected as shown in the table below.
(
♦
... Factory setting)
Setting Description
Function Number
Setting Value
♦
Standard
30
00
Slightly lower control
01
Lower control
02
Warmer control
03
Heating Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be changed as shown in the table below.
(
♦
... Factory setting)
Setting Description
Function Number
Setting Value
♦
Standard
31
00
Lower control
01
Slightly warmer control
02
Warmer control
03
Auto Restart
Enable or disable automatic system restart after a power outage.
(
♦
... Factory setting)
Setting Description
Function Number
Setting Value
♦
Yes
40
00
No
01
* Auto restart is an emergency function such as for power failure etc. Do not start and stop
the indoor unit by this function in normal operation. Be sure to operate by the control unit,
or external input device.
Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when using the Wired remote controller temperature
sensor.
(
♦
... Factory setting)
Setting Description
Function Number
Setting Value
♦
No
42
00
Yes
01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote
controller unit sensor.
Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(
♦
... Factory setting)
Setting Description
Function Number
Setting Value
♦
A
44
00
B
01
C
02
D
03
External input control
“Operation/Stop” mode or “Forced stop” mode can be elected.
(
♦
... Factory setting)
Setting Description
Function Number
Setting Value
♦
Operation/Stop mode
46
00
(Setting forbidden)
01
Forced stop mode
02
Setting record
Record any changes to the settings in the following table.
Setting Description
Setting Value
Filter sign
Cooler room temperature correction
Heater room temperature correction
Auto restart
Indoor room temperature sensor switching function
Remote controller signal code
External input control
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
13. CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air
fl ow switching, and other remote control unit operations.
(2) Air fi lter removal and cleaning, and how to use the air louvers.
(3) Give the operating manual to the customer.