OUTDOOR UNIT
AOU36RLXFZ1
ERROR DETECTION
LED 1
L
ED 2
L
ED 3
L
ED 4
Discharge pipe thermistor
Outdoor unit, heat exchanger thermistor (middle)
Outdoor thermistor error
2-way valve thermistor (indoor unit A)
2-way valve thermistor (indoor unit B)
2-way valve thermistor (indoor unit C)
2-way valve thermistor (indoor unit D)
3-way valve thermistor (indoor unit A)
3-way valve thermistor (indoor unit B)
3-way valve thermistor (indoor unit C)
3-way valve thermistor (indoor unit D)
Compressor thermistor error
Heatsink thermistor error
High pressure switch 1 error
High pressure switch 2 error
Indoor unit capacity error
Trip detection
Compressor roter position detetion error
Trip terminal L error
Outdoor unit fan motor error
Discharge temperature error
Outdoor unit PCB microcomputer communication error
: flashing
: Off
24
2 times
3 times
4 times
5 times
5 times
5 times
5 times
6 times
6 times
6 times
6 times
7 times
8 times
9 times
10 times
11 times
12 times
13 times
14 times
15 times
17 times
18 times
Compressor temperature error
4-way valve error
Active filter error, PFC circuit error
Outdoor unit PCB model information error
19 times
20 times
21 times
22 times
2015.02.18
LED is on a reverse
side of the board.
Hole
LED4
LED3
LED2
LED1