background image

En-2

 CAUTION

•  Do not use flammable substances (such as pesticides and hair sprays). Doing so may 

cause an electric shock, fire or wrong detection by the refrigerant sensor.

•  This product is equipped with a refrigerant leakage sensor. Do not install the product 

at a location filled with smoke, gases or chemicals.

•  After installation is complete, explain to the customer that the breaker must be always 

turned on to ensure the operation of the refrigerant leakage sensor.

•  When connecting the pipes, be careful not to allow the refrigerant to be leaked. 

If the refrigerant is sprayed directly onto the sensor, the sensor may fail.

•  Be careful not to scratch the air conditioner when handling it.

 1.1. Precautions for using R32 refrigerant

The basic installation work procedures are the same as conventional refrigerant (R410A, 
R22) models.
However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of refrigerant R22 models, 
some of the piping and installation and service tools are special. (Refer to 
“2.1. Installation tools”.)
Especially, when replacing a refrigerant R22 model with a new refrigerant R32 model, 
always replace the conventional piping and flare nuts with the R32 and R410A piping and 
flare nuts on the outdoor unit side. 
For R32 and R410A, the same flare nut on the outdoor unit side and pipe can be used.

Models that use refrigerant R32 and R410A have a different charging port thread diam-
eter to prevent erroneous charging with refrigerant R22 and for safety. Therefore, check 
beforehand. [The charging port thread diameter for R32 and R410A is 1/2-20 UNF.]

Be more careful than R22 so that foreign matter (oil, water, etc.) does not enter the 
piping. Also, when storing the piping, securely seal the opening by pinching, taping, etc. 
(Handling of R32 is similar to R410A.)

When charging the refrigerant, take into account the slight change in the composition of 
the gas and liquid phases. And always charge from the liquid phase where refrigerant 
composition is stable.

 CAUTION

1-Installation (Space)

•  That the installation of pipe-work shall be kept to a minimum.
•  That pipe-work shall be protected from physical damage.
•  The appliance shall not be installed in an unventilated space, if that space is smaller 

than X m

2

.

Amount of refrigerant charge 

M (kg)

Minimum room area 

X (m

2

)

 1.22

-

1.22 < M 

 1.23

12.99

1.23 < M 

 1.5

19.31

1.5 < M 

 1.75

26.28

1.75 < M 

 2.0

34.33

2.0 < M 

 2.5

53.63

2.5 < M 

 3.0

77.23

3.0 < M 

 3.5

105.12

3.5 < M 

 4.0

137.29

 (IEC 

60335-2-40)

•  That compliance with national gas regulations shall be observed.
•  That mechanical connections shall be accessible for maintenance purposes.
•  In cases that require mechanical ventilation, ventilation openings shall be kept clear 

of obstruction.

•  When disposing of the product is used, be based on national regulations, properly 

processed.

2-Servicing
2-1 Service personnel

•  Any person who is involved with working on or breaking into a refrigerant circuit 

should hold a current valid certificate from an industry-accredited assessment 
authority, which authorises their competence to handle refrigerants safely in accor-
dance with an industry recognised assessment specification.

•  Servicing shall only be performed as recommended by the equipment manufacturer. 

Maintenance and repair requiring  the assistance of other skilled personnel shall be 
carried out under the supervision of the person competent in the use of flammable 
refrigerants.

•  Servicing shall be performed only as recommended by the manufacturer.

2-2 Work

•  Prior to beginning work on systems containing flammable refrigerants, safety checks 

are necessary to ensure that the risk of ignition is minimized. For repair to the refrig-
erating system, the precautions in 2-2 to 2-8 shall be complied with prior to conduct-
ing work on the system.

•  Work shall be undertaken under a controlled procedure so as to minimize the risk of 

a flammable gas or vapour being present while the work is being performed.

•  All maintenance staff and others working in the local area shall be instructed on the 

nature of work being carried out.

•  Work in confined spaces shall be avoided.
•  The area around the workspace shall be sectioned off.
•  Ensure that the conditions within the area have been made safe by control of flam-

mable material.

 CAUTION

2-3 Checking for presence of refrigerant

•  The area shall be checked with an appropriate refrigerant detector prior to and during 

work, to ensure the technician is aware of potentially flammable atmospheres.

•  Ensure that the leak detection equipment being used is suitable for use with flam-

mable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.

2-4 Presence of fire extinguisher

•  If any hot work is to be conducted on the refrigeration equipment or any associated 

parts, appropriate fire extinguishing equipment shall be available at hand. 

•  Have a dry powder or CO

2

 fire extinguisher adjacent to the charging area.

2-5 No ignition sources

•  No person carrying out work in relation to a refrigeration system which involves 

exposing any pipe work that contains or has contained flammable refrigerant shall 
use any sources of ignition in such a manner that it may lead to the risk of fire or 
explosion.

•  All possible ignition sources, including cigarette smoking, should be kept sufficiently 

far away from the site of installation, repairing, removing and disposal, during which 
flammable refrigerant can possibly be released to the surrounding space.

•  Prior to work taking place, the area around the equipment is to be surveyed to make 

sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall 
be displayed.

2-6 Ventilated area

•  Ensure that the area is in the open or that it is adequately ventilated before breaking 

into the system or conducting any hot work.

•  A degree of ventilation shall continue during the period that the work is carried out.
•  The ventilation should safely disperse any released refrigerant and preferably expel 

it externally into the atmosphere.

2-7 Checks to the refrigeration equipment

•  Where electrical components are being changed, they shall be fit for the purpose 

and to the correct specification.

•  At all times the manufacturer’s maintenance and service guidelines shall be followed.
•  If in doubt consult the manufacturer’s technical department for assistance.
•  The following checks shall be applied to installations using flammable refrigerants.

-  The charge size is in accordance with the room size within which the refrigerant 

containing parts are installed.

-  The ventilation machinery and outlets are operating adequately and are not 

obstructed.

-  If an indirect refrigerating circuit is being used, the secondary circuit shall be 

checked for the presence of refrigerant. 

-  Marking to the equipment continues to be visible and legible. Markings and signs 

that are illegible shall be corrected.

-  Refrigeration pipe or components are installed in a position where they are unlikely 

to be exposed to any substance which may corrode refrigerant containing compo-
nents, unless the components are constructed of materials which are inherently 
resistant to being corroded or are suitably protected against being so corroded.

2-8 Checks to electrical devices

•  Repair and maintenance to electrical components shall include initial safety checks 

and component inspection procedures.

•  If a fault exists that could compromise safety, then no electrical supply shall be con-

nected to the circuit until it is satisfactorily dealt with.

•  If the fault cannot be corrected immediately but it is necessary to continue operation, 

an adequate temporary solution shall be used.

•  This shall be reported to the owner of the equipment so all parties are advised.
•  Initial safety checks shall include.

-  That capacitors are discharged: this shall be done in a safe manner to avoid pos-

sibility of sparking.

-  That there no live electrical components and wiring are exposed while charging, 

recovering or purging the system.

-  That there is continuity of earth bonding.

3-Repairs to sealed components

•  During repairs to sealed components, all electrical supplies shall be disconnected 

from the equipment being worked upon prior to any removal of sealed covers, etc.

•  If it is absolutely necessary to have an electrical supply to equipment during servic-

ing, then a permanently operating form of leak detection shall be located at the most 
critical point to warn of a potentially hazardous situation.

•  Particular attention shall be paid to the following to ensure that by working on electri-

cal components, the casing is not altered in such a way that the level of protection is 
affected.

•  This shall include damage to cables, excessive number of connections, terminals not 

made to original specification, damage to seals, incorrect fitting of glands, etc.

•  Ensure that apparatus is mounted securely.
•  Ensure that seals or sealing materials have not degraded such that they no longer 

serve the purpose of preventing the ingress of flammable atmospheres.

•  Replacement parts shall be in accordance with the manufacturer’s specifications.

NOTE:   The use of silicon sealant may inhibit the effectiveness of some types of leak 

detection equipment.
Intrinsically safe components do not have to be isolated prior to working on 
them.

9378533080-04_IM.indb   2

9378533080-04_IM.indb   2

2022/2/14   15:13:13

2022/2/14   15:13:13

Summary of Contents for AGHG12KVCA

Page 1: ...ut continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware that refrigerants may not contain an odour Keep any required ventilation openings clear of obstruction If the power cable or the connection cable is damaged it must be replaced by the manufacturer its service agent or similar qualified persons...

Page 2: ...quipment being used is suitable for use with flam mable refrigerants i e nonsparking adequately sealed or intrinsically safe 2 4 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available at hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area 2 5 No ign...

Page 3: ...ore carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is ava...

Page 4: ...be purchased separately Additional materials Connection pipe assembly Wall cap Connection cable 4 conductor Saddle Wall pipe Drain hose Decorative tape Tapping screws Vinyl tape Putty Sealant Refrigeration armored tape Insulated staples or clamps for connecting wire refer to your electrical cables Clamps or saddles to secure refrigerant pip ing Refrigeration lubricant 1 1 2 3 Pipe requirement CAUT...

Page 5: ...ote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit When installing pipes shorter tha...

Page 6: ...e top of the indoor unit on the indoor unit wall hook bracket 124 423 703 154 438 Unit mm WARNING Fix the indoor unit with 4 screws surely If improperly installed might cause to injury due to the toppling or falling Install the indoor unit at the place that has adequate strength Install the indoor unit so that the installed unit can withstand the weight of adult body weight If improperly installed...

Page 7: ... from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R32 clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional flare tools to flare R32 pipes the dimension A should be approx imately 0 5 mm more than indicated in t...

Page 8: ...cable clamp always fasten the cable at the plastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the ground earth wire Improper earthing grounding work can cause electric shocks Do not use the ground earth screw for the indoor unit to the outdoor unit unless it is specified When the flare nut is tightened properly by your hand ...

Page 9: ...ON WORK 4 1 Before install optional remote controller When you use optional remote controller some functions may not be used Please use the recommended optional remote controller CAUTION Before installing be sure to disconnect all power supply Don t touch the heat exchanger During installing or removing operation be sure not to have wire caught by parts or draw it hard Or it may result troubles to...

Page 10: ...he following condition DC 12 V to 24 V 1 mA to 15 mA Operation behavior Input signal type Edge ON OFF When function setting is Operation Stop mode 1 Input signal Command OFF ON Operation ON OFF Stop When function setting is Forced stop mode Input signal Command OFF ON Forced stop ON OFF Normal When the forced stop is triggered indoor unit stops and Operation Stop operation by a remote controller i...

Page 11: ...fore reconnecting it The function setting will not become active unless the power supply is disconnected and then reconnected 5 1 Function details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function num ber Settin...

Page 12: ...s Error status Setting record Record any changes to the settings in the following table Function number Function setting Setting value 11 Filter sign 30 Room temperature control for indoor unit sensor Cooling 31 Heating 35 Room temperature control for wired remote controller sensor Cooling 36 Heating 40 Auto restart 42 Room temperature sensor switching 44 Remote controller custom code 46 External ...

Page 13: ...d remote controller error codes will ap pear on the remote control display Refer to the lamp blinking patterns and error codes in the table An error display is displayed only during operation The error code table contains errors irrelevant to this product as well Error display on the indoor unit TIMER LED1 TIMER Lamp orange LED2 OPERATION lamp green LED3 ECONOMY lamp green OPERATION ECONOMY For wi...

Page 14: ...otor 1 error Error display Error code Description LED1 orange LED2 green LED3 green 8 9 98 Outdoor unit fan motor 2 error 9 9 99 4 way valve error 10 9 9A Coil expansion valve error 1 10 A1 Discharge temp error 3 10 A3 Compressor temp error 4 10 A4 High pressure error 5 10 A5 Low pressure error 8 10 A8 Refrigerant leakage suspicion 11 10 AC Heat sink temp error 2 13 J2 Branch boxes error Multi spl...

Reviews: