background image

En-8

3.4.2. Indoor unit wiring

(1) Remove the terminal cover.
(2) Remove the cable clamp.
(3) Bend the end of the connection cable as shown in the figure.
(4) Connect the end of the connection cable fully into the terminal block.
(5) Fasten the connection cable with a cable clamp.

Connection 
cable

Cable 
clamp

40 mm

30 mm

Cable clamp

Unit: mm

Terminal cover

Ground (Earth) 
wire

Screw

3.4.3.  How to connect wiring to the terminals

 

Caution when wiring cable

To strip off the insulation of a lead wire, always use a special tool such as a wire stripper. 
If there is no special tool, carefully strip off the insulation by using a knife or other utensil. 
(1)  Use ring terminals with insulating sleeves as shown in the figure to connect to the 

terminal block. 

(2)  Securely clamp the ring terminals to the wires by using an appropriate tool so that the 

wires do not come loose. 

Strip : 10 mm 

Ring terminal

Sleeve

(3)  Connect specified wires securely, and fasten them so that there is no stress applied on 

the terminals. 

(4)  Use a screwdriver with an appropriate bit size to tighten the terminal screws. Using of 

screwdriver with inappropriate bit size will damage the screw heads, and the screws 
will not be tightened properly.

(5)  Do not overtighten the terminal screws. Otherwise, the screws may break.

Screw with special washer

Wire

Ring terminal

Terminal blocks

Wire

Screw with special washer

Ring terminal

(6)  Refer to the table for the terminal screw tightening torques.

Tightening torque [N·m (kgf·cm)]

M4 screw

1.2 to 1.8 (12 to 18)

 CAUTION

•  Match the terminal block numbers and connection cable colors with those of the 

outdoor unit. Incorrect wiring may cause a fire.

•  Connect the connection cables firmly to the terminal block. Imperfect installation may 

cause a fire.

•  When fixing the connection cable with the cable clamp, always fasten the cable at the 

plastic jacket portion, but not at the insulator portion. If the insulator is chafed, electric 
leakage may occur.

•  Always connect the ground (earth) wire. Improper earthing (grounding) work can 

cause electric shocks.

•  Do not use the ground (earth) screw for the indoor unit to the outdoor unit unless it is 

specified.

When the flare nut is tightened properly by your hand, hold the body side coupling with 
a wrench, then tighten with a torque wrench. (Refer to the following table for the flare nut 
tightening torques.)

Wrench (fixed)

Connection pipe

Flare nut

Indoor unit pipe

Tighten with two wrenches.

Torque wrench

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

Do not remove the cap from the connection pipe before connecting the pipe.

3.4. Electrical wiring

 WARNING

•  Before connecting the wires, make sure the power supply is OFF.
•  Every wire must be connected firmly.
•  No wire should be allowed to touch refrigerant tubing, the compressor, or any mov-

ing part.

•  Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire 

hazard may also exist. Therefore, be sure all wiring is tightly connected.

•  Connect wires to the matching numbers of terminals.

 CAUTION

Be careful not to generate a spark as follows for using a flammable refrigerant.

•  Do not remove the fuse while the power is on.
•  Do not disconnect the wiring while the power is on. 
•  It is recommended to position the outlet connection in a high position. Place the 

cords so that they do not get tangled.

3.4.1. Wiring system diagram

 

Standard pair

Indoor unit

Ground (Earth) line

Outdoor unit

Power line

Control line

Connection cable 

 

Wired remote controller cable (option)

2-wire type

 

Multi-split type

Indoor unit

Outdoor unit

Indoor unit

Ground (Earth) line

Control line

Connection cable 

Power line

UNIT

 A

UNIT

 B

9378533080-04_IM.indb   8

9378533080-04_IM.indb   8

2022/2/14   15:13:14

2022/2/14   15:13:14

Summary of Contents for AGHG12KVCA

Page 1: ...ut continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware that refrigerants may not contain an odour Keep any required ventilation openings clear of obstruction If the power cable or the connection cable is damaged it must be replaced by the manufacturer its service agent or similar qualified persons...

Page 2: ...quipment being used is suitable for use with flam mable refrigerants i e nonsparking adequately sealed or intrinsically safe 2 4 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available at hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area 2 5 No ign...

Page 3: ...ore carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is ava...

Page 4: ...be purchased separately Additional materials Connection pipe assembly Wall cap Connection cable 4 conductor Saddle Wall pipe Drain hose Decorative tape Tapping screws Vinyl tape Putty Sealant Refrigeration armored tape Insulated staples or clamps for connecting wire refer to your electrical cables Clamps or saddles to secure refrigerant pip ing Refrigeration lubricant 1 1 2 3 Pipe requirement CAUT...

Page 5: ...ote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit When installing pipes shorter tha...

Page 6: ...e top of the indoor unit on the indoor unit wall hook bracket 124 423 703 154 438 Unit mm WARNING Fix the indoor unit with 4 screws surely If improperly installed might cause to injury due to the toppling or falling Install the indoor unit at the place that has adequate strength Install the indoor unit so that the installed unit can withstand the weight of adult body weight If improperly installed...

Page 7: ... from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R32 clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional flare tools to flare R32 pipes the dimension A should be approx imately 0 5 mm more than indicated in t...

Page 8: ...cable clamp always fasten the cable at the plastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the ground earth wire Improper earthing grounding work can cause electric shocks Do not use the ground earth screw for the indoor unit to the outdoor unit unless it is specified When the flare nut is tightened properly by your hand ...

Page 9: ...ON WORK 4 1 Before install optional remote controller When you use optional remote controller some functions may not be used Please use the recommended optional remote controller CAUTION Before installing be sure to disconnect all power supply Don t touch the heat exchanger During installing or removing operation be sure not to have wire caught by parts or draw it hard Or it may result troubles to...

Page 10: ...he following condition DC 12 V to 24 V 1 mA to 15 mA Operation behavior Input signal type Edge ON OFF When function setting is Operation Stop mode 1 Input signal Command OFF ON Operation ON OFF Stop When function setting is Forced stop mode Input signal Command OFF ON Forced stop ON OFF Normal When the forced stop is triggered indoor unit stops and Operation Stop operation by a remote controller i...

Page 11: ...fore reconnecting it The function setting will not become active unless the power supply is disconnected and then reconnected 5 1 Function details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function num ber Settin...

Page 12: ...s Error status Setting record Record any changes to the settings in the following table Function number Function setting Setting value 11 Filter sign 30 Room temperature control for indoor unit sensor Cooling 31 Heating 35 Room temperature control for wired remote controller sensor Cooling 36 Heating 40 Auto restart 42 Room temperature sensor switching 44 Remote controller custom code 46 External ...

Page 13: ...d remote controller error codes will ap pear on the remote control display Refer to the lamp blinking patterns and error codes in the table An error display is displayed only during operation The error code table contains errors irrelevant to this product as well Error display on the indoor unit TIMER LED1 TIMER Lamp orange LED2 OPERATION lamp green LED3 ECONOMY lamp green OPERATION ECONOMY For wi...

Page 14: ...otor 1 error Error display Error code Description LED1 orange LED2 green LED3 green 8 9 98 Outdoor unit fan motor 2 error 9 9 99 4 way valve error 10 9 9A Coil expansion valve error 1 10 A1 Discharge temp error 3 10 A3 Compressor temp error 4 10 A4 High pressure error 5 10 A5 Low pressure error 8 10 A8 Refrigerant leakage suspicion 11 10 AC Heat sink temp error 2 13 J2 Branch boxes error Multi spl...

Reviews: