2-25. E: 94. Trip detection (Outdoor unit)
Indicator
→ired remote
controller
Error code
E: 94
Detective actuator Outdoor unit
Main PCB
Protection stop by over-current generation after inverter
compressor start processing completed generated
consecutively 10 times.
NOTE:
The number of generations is reset when the
compressor starts up.
Compressor
Forecast of cause
Outdoor unit fan operation defective, foreign matter on
heat-exchanger, excessive rise of ambient temperature
Main PCB failure
Inverter compressor failure (lock, winding short)
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
•
No obstructions in air passages?
•
Heat exchange fins clogged
•
Outdoor unit fan motor check
•
Ambient temperature not raised by the effect of other heat sources?
•
Discharged air not sucked in?
Check point 2. Replace main PCB
If Check point 1 do not improve the symptom, change main PCB.
Check point 3. Replace compressor
If Check point 2 do not improve the symptom, change compressor.
End
2-25. E: 94. Trip detection (Outdoor unit)
- (03-30) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ACUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Page 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Page 48: ......
Page 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Page 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...