6. ELECTRICAL WIRING

 WARNING

Electrical work must be performed in accordance with 

• 

this Manual by a person certified under the national or 

regional regulations. Be sure to use a dedicated circuit 

for the unit.  

An insufficient power supply circuit or improperly per

-

formed electrical work can cause serious accidents such 

as electric shock or fire.

Before starting work, check that power is not being sup-

• 

plied to the indoor unit and outdoor unit.
Use the included connection cables and power cables or 

• 

ones specified by the manufacturer. Improper connec

-

tions, insufficient insulation, or exceeding the allowable 

current can cause electric shock or fire.

For wiring, use the prescribed type of wires, connect 

• 

them securely, making sure that there are no external 

forces of the wires applied to the terminal connections. 

Improperly connected or secured wires can cause seri-

ous accidents such as overheating the terminals, electric 

shock, or fire.
Do not modify the power cables, use extension cables, 

• 

or use any branches in the wiring. Improper connections, 

insufficient insulation, or exceeding the allowable current 

can cause electric shock or fire.

Match the terminal block numbers and connection cable 

• 

colors with those of the outdoor unit. Erroneous wiring 

may cause burning of the electric parts.
Securely connect the connection cables to the terminal 

• 

blocks. In addition, secure the cables with wiring holders. 

Improper connections, either in the wiring or at the ends 

of the wiring, can cause a malfunction, electric shock, or 

fire.

Always fasten the outside covering of the connection 

• 

cable with the cable clamp. (If the insulator is chafed, 

electric leakage may occur.)

Securely install the electrical box cover on the unit. 

• 

An improperly installed electrical box cover can cause 

serious accidents such as electric shock or fire through 

exposure to dust or water.

Install sleeves into any holes made in the walls for wiring. 

• 

Otherwise, a short circuit could result.
Install a ground leakage breaker. In addition, install the 

• 

ground leakage breaker so that the entire AC main power 

supply is cut off at the same time. Otherwise, electric 

shock or fire could result.

Install a ground leakage breaker.  

• 

If a ground leakage breaker is not installed, it may cause 

electric shock or fire.

Always connect the ground wire. 

• 

Improper grounding work can cause electric shocks.
Install the remote controller wires so as not to be direct 

• 

touched with your hand.

6.1. Electrical requirement

Connection cable (mm

2

)

MAX.

MIN.

2.5

1.5

Use conformed cable with Type 245 IEC57.

• 

Perform all electrical work according to the standard.

• 

Install circuit breakers, which have the terminal spacing 

• 

of more than 3 mm, in a place of near the indoor unit and 

outdoor unit.

 CAUTION

Be sure to execute the electrical work according to the 

• 

Laws of each country and the Installation Instructions. 

In addition, be sure to set as exclusive line and use the 

rated voltage and circuit breaker.

6.2. Wiring method

6.2.1. Connection diagrams

Connection cable (to outdoor unit)

• 

3

2

1

Power line

 

Control line

 

Indoor unit 

side

Wired remote controller cable

• 

3

2

1

Black

White

Red

*

Indoor unit 

side

*

 Ground the remote controller if it has a ground wire.

6.2.2. Connection cable preparation

Power supply cable

or connection cable

30 m

m

40 mm or 

more

Earth wire

• Use a 4-core wire cable

.

Keep the earth wire longer than the other wires.

 

How to connect wiring to the terminals.

(For strand wiring)

Use crimp-type terminals with insulating sleeves as shown 

(1) 

in the figure below to connect to the terminal block.

Securely crimp the crimp-type terminals to the wires using 

(2) 

an appropriate tool so that the wires do not come loose.

Sleeve

Crimp-type

terminal

Strip 10 mm

1125-9379122009.indd   9

2008/11/26   7:57:05

www.enindel.com

Summary of Contents for ABYA45LCT

Page 1: ...ulation 5 INSTALLING DRAIN PIPES 8 6 ELECTRICAL WIRING 9 6 1 Electrical requirement 6 2 Wiring method AIR CONDITIONER INDOOR UNIT Ceiling type PART NO 9379122009 02 7 REMOTE CONTROLLER SETTING 11 7 1 Load batteries R03 LR03 2 7 2 Remote control unit holder installation 8 FUNCTION SETTING 11 8 1 Entering the function setting mode 8 2 Function setting 9 SELECTING THE REMOTE CONTROL UNIT SIGNAL CODE ...

Page 2: ...ill become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refriger ant pipe connections or other area Touching the refriger ant directly can cause frostbit...

Page 3: ...bustible gas leakage Do not install the unit near a source of heat steam or flammable gas Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise und...

Page 4: ...n for Suspension bolt Ceiling Wall Template Drilling position for piping 3 3 3 Location of ceiling suspension bolts 30 Suspension bolt pitch 1600 Dimensions Space Required for Installation 30 10 155 300 INDOOR UNIT TOP VIEW INDOOR UNIT Suspension bolt should extend outward 30 to 75 mm Unit mm Install the indoor unit on a place having a sufficient 1 strength so that it withstands against the weight...

Page 5: ... nut to each bolt The two special nuts are provided with the unit The M10 nut must be obtained locally Refer to the figure Bolt Strength N kgf 980 to 1470 100 to 150 Ceiling panel Special nut A Included Special nut B Included M10 Nut Obtained locally 10 to 15 Unit mm 3 3 6 Installing the indoor unit Lift unit so that suspension bolts pass through the suspen 1 sion fittings at the sides four places...

Page 6: ... that is 15 mm or thicker and if the expected humidity exceeds 80 use heat insulation that is 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 20 C 4 PIPE INSTALLATION CAUTION Be more careful that foreign matter oil water etc does not ...

Page 7: ...ipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than three times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection CAUTION Be sure to apply the pipe against the port on the indoor unit and the outdoor ...

Page 8: ...correctly within the indoor unit Indoor unit rear view VT wire Drain hose If the drain hose will not be connected to the right rear 3 piping cut the hole cover at the points indicated in Fig a and attach it to the piping hole as shown in Fig b a Cut x 5 Hole cover b 4 4 Installing heat insulation CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this...

Page 9: ...l box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls for wiring Otherwise a short circuit could result Install a ground leakage breaker In addition install the ground leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result In...

Page 10: ...Do not attempt to recharge dry batteries Use the specified wires connect them securely and fasten 3 them so that there is no stress placed on the terminals Use an appropriate screwdriver to tighten the terminal 4 screws Do not use a screwdriver that is too small other wise the screw heads may be damaged and prevent the screws from being properly tightened Do not tighten the terminal screws too muc...

Page 11: ...control unit are replaced If you use a signal code other than signal code A reset the signal code after replacing the batteries If you do not know the air conditioner signal code setting try each of the signal codes until you find the code which operates the air conditioner NOTE Never mix new and used batteries or batteries of different types Batteries should last about one year under normal use I...

Page 12: ...FUNCTION SETTING be sure to turn off the power and turn it on again 8 2 Function setting STEP 2 Selecting the Function Number and Setting Value Press the SET TEMP 1 buttons to select the func tion number Press the MODE button to switch between the left and right digits Press the FAN button to proceed to setting the value 2 Press the FAN button again to return to the function number selection Press...

Page 13: ...ode of the remote control unit to operate only the air conditioner you wish to set four selections possible When two or more air conditioners are installed in a room please contact your retailer to set the individual air conditioner signal codes Confirm the setting of the remote control unit signal code and the printed circuit board setting If these are not confirmed the remote control unit cannot...

Page 14: ...roller abnormal 2 times 2 times Indoor room temperature sensor error 2 times 3 times Indoor heat exchanger tempera ture sensor middle error 2 times 4 times Indoor heat exchanger tempera ture sensor inlet error 2 times 6 times Float switch operated 3 times 2 times Outdoor discharge pipe tempera ture sensor error 3 times 3 times Outdoor heat exchanger temperature sensor outlet error 3 times 4 times ...

Page 15: ...t circuit address set up error 31 Master unit Slave unit set up error 32 Connected the indoor number set up error 33 P F C printed circuit board error If C0 appears in the unit number display there is a remote controller error Unit number Error code Content C0 1d Incompatible indoor unit is connected C0 1c Indoor unit remote control ler communication error 13 SPECIAL INSTALLATION METHODS CAUTION W...

Page 16: ...ndoor unit with the unit number 0 last Within 1 minute 2 When the indoor units are turned on error codes 01 and 31 will be displayed however these error codes will be deleted by setting the remote controller Therefore continue with the setting procedure Set the refrigerant circuit address Assign the same 2 number to all of the indoor units connected to an outdoor unit Refrigerant circuit address F...

Reviews: