DANGER
This part (Choke coil) generates high voltages.
Never touch this part.
SPECIAL INSTALLATION
SETTING
PUMP DOWN (Refrigerant collecting operation)
Perform the following procedures to collect the refrigerant when moving
the indoor unit or the outdoor unit.
(1) Press the push-button switch (SW2) on the circuit board once.
The LED on the circuit board starts flashing (one second ON/one se-
cond OFF). This indicates the start of PUMP DOWN operation.
When the switch is pressed while the compressor is in operation, PUMP
DOWN operation starts automatically.
When the switch is pressed while the compressor is in stop, the com-
pressor starts to operate automatically, and then move on to PUMP
DOWN operation.
(2) PUMP DOWN operation continues for about 1 minute. When PUMP
DOWN operation is completed, the compressor stops automatically.
Then close the 2-way valve and 3-way valve immediately.
(3) Turn the power off.
ERROR CONTENTS
(outdoor unit)
1. Make a TEST RUN in accordance with the in-
stallation instruction sheet for the indoor unit.
2. OUTDOOR UNIT LEDS
When a malfunction occurs in the outdoor unit, the LED on the circuit
board lights to indicate the error. Refer to the following table for the de-
scription of each error according to the LED.
Error contents
Communication error
(Indoor unit - Outdoor unit)
Discharg pipe temperature sensor
Outdoor heat exchanger temperature sensor
Outdoor temperature sensor
Compressor temperature sensor
Heat sink temperature sensor
Pressure switch abnormal
IPM error
Compressor rotor position cannot detect
Compressor cannot operate
Outdoor fan abnormal (upper fan)
Outdoor fan abnormal (lower fan)
Protect operation
No error
LED
1 flash
2 flash
3 flash
4 flash
7 flash
8 flash
9 flash
12 flash
13 flash
14 flash
15 flash
16 flash
5 sec. ON/
1 sec. OFF
repeated
lighting
CAUTION
Always turn on the power 12 hours prior to the start of the
operation in order to ensure compressor protection
PUMP DOWN SW (SW2)
2005.10.27
12
www.enindel.com
Summary of Contents for ABY45LBAG
Page 3: ...DIMENSIONS 1 660 240 700 1 600 130 300 Unit mm INDOOR UNIT 2005 10 26 2 www enindel com ...
Page 15: ...Model ABY45LBAG 2005 10 27 14 506 407 505 408 435 434 876 1 69 www enindel com ...
Page 16: ...Model ABY45LBAG 2005 10 27 15 387 160 91 91 91 321 361 386 www enindel com ...
Page 19: ...1 6 7 5 2 3 4 3 Model AOY45LJBYL 2005 10 27 18 www enindel com ...
Page 20: ...16 13 12 11 10 9 15 8 14 49 Model AOY45LJBYL 2005 10 27 19 www enindel com ...
Page 21: ...22 20 21 23 24 19 17 18 26 42 25 Model AOY45LJBYL 2005 10 27 20 www enindel com ...
Page 26: ...0510G2926 www enindel com ...