1-4. Error code table (Outdoor unit)
The operation status is determined by the lighting up and blinking of the LED lamp.
After check that ERROR LED lamp blinks, press the ENTER button once.
NOTE:
For the positions of LED lamp and buttons, refer to
"Function settings (for outdoor unit)"
Chapter 5. FIELD WORKING on page 05-52.
Error contents
POWER/
MODE
ERROR
MONITOR
A
B
C
D
E
F
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
(Occurs immediately after starting
operation)
●
■
■
1
■
1
○
○
●
●
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
(Occurs during operation)
●
■
■
1
■
1
○
●
○
○
E: 12. Wired remote controller
communication error (Indoor unit)
●
■
■
5
■
15
○
○
○
●
E: 18. External communication error
(Indoor unit)
●
■
■
5
■
15
○
○
○
●
E: 22. Indoor unit capacity error (Indoor
unit)
●
■
■
5
■
15
○
○
○
●
E: 23. Combination error (Outdoor unit)
●
■
■
5
■
15
○
○
○
●
E: 26. Address setting error in wired
remote controller (Indoor unit)
●
■
■
5
■
15
○
○
○
●
E: 29. Connected unit number error
(Indoor unit)
●
■
■
5
■
15
○
○
○
●
E: 32. Indoor unit main PCB error (Indoor
unit)
●
■
■
5
■
15
○
○
○
●
E: 33. Indoor unit motor electricity
consumption detection error (Indoor unit)
●
■
■
5
■
15
○
○
○
●
E: 35. MANUAL AUTO button error
(Indoor unit)
●
■
■
5
■
15
○
○
○
●
E: 3A. Indoor unit communication circuit
(wired remote controller) error
●
■
■
5
■
15
○
○
○
●
E: 41. Room temperature sensor error
(Indoor unit)
●
■
■
5
■
15
○
○
○
●
E: 42. Indoor unit heat exchanger sensor
error (Indoor unit)
●
■
■
5
■
15
○
○
○
●
E: 51. Indoor unit fan motor error (Indoor
unit)
●
■
■
5
■
15
○
○
○
●
E: 62. Outdoor unit model information
error (Outdoor unit)
●
■
■
6
■
2
○
○
●
●
E: 64. Active filter voltage error (Outdoor
unit)
●
■
■
6
■
4
○
○
○
●
E: 65. IPM error (Outdoor unit)
●
■
■
6
■
5
○
○
●
●
E: 71. Discharge thermistor error
(Outdoor unit)
●
■
■
7
■
1
○
○
○
●
E: 72. Compressor thermistor error
(Outdoor unit)
●
■
■
7
■
2
○
○
○
●
E: 73. Outdoor unit heat exchanger
thermistor error (Outdoor unit)
●
■
■
7
■
3
○
○
●
○
E: 74. Outdoor temperature thermistor
error (Outdoor unit)
●
■
■
7
■
4
○
○
○
●
E: 76. 2-way valve thermistor error
(Outdoor unit)
●
■
■
7
■
6
○
○
○
●
E: 76. 3-way valve thermistor error
(Outdoor unit)
●
■
■
7
■
6
○
○
●
○
1-4. Error code table (Outdoor unit)
- (03-4) -
1. Error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...