2-31. E: 76. 2-way valve thermistor error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
7 time flash
Timer indicator
6 time flash
Economy indicator
Continuous flash
Error code
E: 76
Detective actuator
Outdoor unit main PCB
When 2-way valve temperature thermistor open or short
circuit is detected at power on or while running the
compressor.
2-way valve temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the outdoor temperature thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-117.
If the voltage does not appear, replace main PCB.
↓
End
2-31. E: 76. 2-way valve thermistor error (Outdoor unit)
- (03-47) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...