14. FUNCTION SETTING
Perform the “FUNCTION SETTING” according to the installation conditions using the
remote controller.
CAUTION
Con
fi
rm whether the wiring work for outdoor unit has been
fi
nished.
Con
fi
rm that the cover for the electrical enclosure on the outdoor unit is in place.
• This procedure changes to the function settings used to control the indoor unit according
to the installation conditions. Incorrect settings can cause the indoor unit to malfunction.
• After the power is turned on, perform the “FUNCTION SETTING” according to the
installation conditions using the remote controller.
• The settings may be selected between the following two: Function Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are selected.
• Refer to the installation manual enclosed with the remote control unit when the wired
remote control unit (option) is used.
• Adjust the signal code of the indoor unit and the signal code of the remote controller.
Entering the Function Setting Mode
While pressing the POWERFUL button and SET TEMP. ( ) simultaneously, press the
RESET button to enter the function setting mode.
Selecting the Function Number and Setting Value
(1)
Press the SET TEMP. (
/
) buttons to select
the function number. (Press the 10°C HEAT button
to switch between the left and right digits.)
(2)
Press the POWERFUL button to proceed to setting
the value. (Press the POWERFUL button again to
return to the function number selection.)
(3)
Press the SET TEMP. (
/
) buttons to select
the setting value. (Press the 10°C HEAT button to
switch between the left and right digits.)
(4)
Press the MODE button, in the order listed to con
fi
rm
the settings.
Please con
fi
rm that the beep sounds.
(5)
Next, please press START/STOP (
) button.
Please con
fi
rm that the beep sounds.
(6)
Press the RESET button to cancel the function set-
ting mode.
(7)
After completing the FUNCTION SETTING, be sure to turn off the power and turn it
on again.
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again.
The Function Setting does not become active unless the power is turned off then on
again.
Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the
fi
lter. Select the
time setting for the
fi
lter sign display interval in the table below according to the amount of
dust or debris in the room. If you do not wish the
fi
lter sign to be displayed, select the set-
ting value for “No indication”.
(
♦
... Factory setting)
Setting Description
Function
Number
Setting Value
Standard (400 hours)
11
00
Long interval (1,000 hours)
01
Short interval (200 hours)
02
♦
No indication
03
Cooling Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a cor-
rection.
The settings may be selected as shown in the table below.
(
♦
... Factory setting)
Setting Description
Function
Number
Setting Value
♦
Standard
30
00
Slightly lower control
01
Lower control
02
Warmer control
03
Function number
Setting
value
Installing the external connect kit terminal (sold separately)
Connect the wire of external input/output to the board of external connect kit.
(
EXTERNAL INPUT CONNECT TO NO. CNA01
EXTERNAL OUTPUT CONNECT TO NO. CNB01, CNB02
)
External
connect kit cord
Error Status Output
connector : CNB02 (Black connector)
Operation Status Output
connector : CNB01 (White connector)
Control Input
(Operation/Stop or Forced stop)
connector : CNA01 (White connector)
Rib
Fixing the wires
After connecting the terminals, thread the wires through the notches and clasp
of the control box as circled on the
fi
gure below.
Then
fi
x the wires onto the control box with the provided binder.
Relay control board
Binder
12.2.5. Installing the control box, connector and the control cover
(1) Attach the control box to the indoor unit.
(2) Connect the connector wires.
(3) Attach the control cover.
(4) Attach the 3 screws. Screw 2 is the screw which installs the ground wire.
12.2.6. Labelling
Paste the wiring label beside the label for schematic diagram inside the front panel.
12.2.7. Installing the front panel and intake grille
(Refer to 9.2. intake grille installation and 9.4. front panel installation)
13. SELECTING THE REMOTE CONTROLLER SIGNAL CODE
When two or more air conditioners are installed in a room and the remote controller is op-
erating an air conditioner other than the one you wish to set, change the signal code of the
remote controller to operate only the air conditioner you wish to set (4 selections possible).
When two or more air conditioners are installed in a room, please contact your retailer to
set the individual air conditioner signal codes.
Selecting the Remote Controller Signal Code
Use the following steps to select the signal code of the remote controller. (Note that the
air conditioner cannot receive a signal code if the air conditioner has not been set for the
signal code.)
(1) Press the START/STOP (
) button until only the clock
is displayed on the remote controller display.
(2) Press the MODE button for at least 5 seconds to display
the current signal code (initially set to ).
(3) Press the SET TEMP. ( /
) buttons to change the
signal code between
.
Match the code on the display to the air conditioner
signal code.
(4) Press the MODE button again to return to the clock
display. The signal code will be changed.
• If no buttons are pressed within 30 seconds after the signal code is displayed, the
system returns to the original clock display. In this case, start again from step 1.
• The air conditioner signal code is set to A prior to shipment.