11. FUNCTION SETTING

Perform the “FUNCTION SETTING” according to the installation conditions using the 
remote controller.

 CAUTION

• Con

fi

 rm whether the wiring work for Outdoor unit or Branch box has been 

fi

 nished.

• Con

fi

 rm that the cover for the electrical enclosure on the outdoor unit is in place.

• This procedure changes to the function settings used to control the indoor unit according to 

the installation conditions. Incorrect settings can cause the indoor unit to malfunction.

• After the power is turned on, perform the “FUNCTION SETTING” according to the 

installation conditions using the remote controller.

• The settings may be selected between the following two: Function Number or Setting 

Value.

• Settings will not be changed if invalid numbers or setting values are selected.
• Refer to the installation manual enclosed with the remote controller when the wired 

remote controller (option) is used.

Entering the Function Setting Mode

While pressing the FAN button and SET TEMP. (

) simultaneously, press the RESET 

button to enter the function setting mode.

STEP 1

Selecting the Remote Controller Custom Code

Use the following steps to select the custom code of the remote controller. (Note that the 
air conditioner cannot receive a signal if the air conditioner has not been set for the cus-
tom code.) 
The custom codes that are set through this process are applicable only to the signals in 
the FUNCTION SETTING. For details on how to set the cus-
tom codes through the normal process, refer to Remote 
controller custom code.

1

  Press SET TEMP. (

) (

) button to change the custom 

code between A   B   C   D. Match the code on the 
display to the air conditioner custom code. (initially set to 
A) 
(If the custom code does not need to be selected, press 
the MODE button and proceed to STEP 2.)

2

  Press the TIMER MODE button and check that the indoor 

unit can receive signals at the displayed custom code.

3

  Press the MODE button to accept the custom code, and 

proceed to STEP 2.

The air conditioner custom code is set to A prior to ship-
ment. Contact your retailer to change the custom code.

The remote controller resets to custom code A when the batteries in the remote con-
troller are replaced. If you use a custom code other than custom code A, reset the 
custom code after replacing the batteries.
If you do not know the air conditioner custom code setting, try each of the custom 
codes (A   B   C   D) until you 

fi

 nd the code which operates the air conditioner.

STEP 2

Selecting the Function Number and Setting Value

1

  Press the SET TEMP. (

) (

) buttons to select the function number.

   (Press the MODE button to switch between the left and right digits.)

2

  Press the FAN button to proceed to setting the value. 

   (Press the FAN button again to return to the function number selection.)

3

  Press the SET TEMP. (

) (

) buttons to select the setting value.

   (Press the MODE button to switch between the left and right digits.)

4

  Press the TIMER 

MODE button, 
and START/STOP 
button, in the order 
listed to con

fi

 rm the 

settings.

5

  Press the RESET 

button to cancel the 
function setting mode.

6

  After completing the 

FUNCTION SETTING, 
be sure to turn off the 
power and turn it on again.

 CAUTION

After turning off the power, wait 10 seconds or more before turning on it again.
The Function Setting does not become active unless the power is turned off then on 
again.

11.1. 

Function details

Filter Sign

Select appropriate intervals for displaying the 

fi

 lter sign on the indoor unit according to the 

estimated amount of dust in the air of the room.
If the indication is not required, select “No indication” (03).

(

...  Factory setting)

Function Number

Setting 

Value

Setting Description

11

00

Standard (400 hours)

01

Long interval (1000 hours)

02

Short interval (200 hours)

03

No indication

Auto Restart

Enable or disable automatic restart after a power interruption.

(

...  Factory setting)

Function Number

Setting 

Value

Setting Description

40

00

Enable

01

Disable

* Auto restart is an emergency function such as for power outage etc. Do not attempt to 

use this function in normal operation. Be sure to operate the unit by remote controller or 
external device.

Room temperature sensor switching

(Only for Wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to “Both” 
(01).

(

...  Factory setting)

Function Number

Setting 

Value

Setting Description

42

00

Indoor unit

01

Both

00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller

Remote controller custom code

(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.

(

...  Factory setting)

Function Number

Setting 

Value

Setting Description

44

00

A

01

B

02

C

03

D

Function 

number

Setting 

value

9318739183_IM.indb   9

9318739183_IM.indb   9

11/19/2014   6:04:32 PM

11/19/2014   6:04:32 PM

Summary of Contents for 9318739183

Page 1: ... strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised plat...

Page 2: ...gerant R410A have a different charging port thread diameter to pre vent erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching...

Page 3: ...s or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or s...

Page 4: ...ping cut off the piping outlet cutting groove with a hacksaw CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur Attach the Drain hose insulation to the drain hose Drain hose insulation Drain hose For left piping and left rear piping alig...

Page 5: ...ct with a flame CAUTION Connect the piping so that the control box cover can easily be removed for servic ing when necessary In order to prevent water from leaking into the control box make sure that the pip ing is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a wrench then tighten with a torque wrench See the table below for the flare nut ti...

Page 6: ... m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Connect the conne...

Page 7: ...or simple remote controller Recommended cable length of wired remote controller is 32 ft 10 m Make sure to do insulate of connecting part when extended the cable 10 2 Remote controller cable modification 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable 2 Connect the remote controller cable and connecting cab...

Page 8: ...onnecting cable to control board connector 1 Pass the cable from the hole in the back of indoor unit 2 Connect the cable to the control board connector 3 Hook the cable to the rib connect the cable rib CN6 CN16 CN14 PCB hole Option type Connector No Wired remote controller Simple remote controller CN6 External input CN14 External output CN16 4 Use cable clamper and screw to fasten the cable of wir...

Page 9: ...do not know the air conditioner custom code setting try each of the custom codes A B C D until you find the code which operates the air conditioner STEP 2 Selecting the Function Number and Setting Value 1 Press the SET TEMP buttons to select the function number Press the MODE button to switch between the left and right digits 2 Press the FAN button to proceed to setting the value Press the FAN but...

Page 10: ...nges When High insulation 01 is selected Overheating overcooling is prevented at the start up All room temp control settings Function 30 31 92 93 will reset to No correction 0 0 F 0 0 C Factory setting Function Number Setting Value Setting Description 95 00 Standard insulation 01 High insulation Room temperature control for indoor unit sensor Depending on the installed environment correction of th...

Page 11: ...ress the test run button with the tip of a ballpoint pen etc Transmitter section TEST RUN button To end test operation press the remote controller START STOP button When the air conditioner is running by pressing the TEST RUN button the OPERA TION Lamp and TIMER Lamp will simultaneously flash slowly Using the wired remote control Option For the operation method refer to the operating manual 1 Stop...

Page 12: ... temp sensor error 8 4 Current sensor error 8 6 Discharge pressure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection 9 5 Compressor rotor position detection error 9 7 Outdoor unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Di...

Reviews: