background image

En-10

External input control

“Operation/Stop” mode or “Forced stop” mode can be selected.

(

...  Factory setting)

Function Number

Setting 

Value

Setting Description

46

00

Operation/Stop mode

01

(Setting prohibited)

02

Forced stop mode

Room temperature sensor switching (Aux.)

To use the temperature sensor on the wired remote controller only, change the setting to 
“Wired remote controller” (01). This function will only work if the function setting 42 is set 
at “Both” (01)

(

...  Factory setting)

Function Number

Setting 

Value

Setting Description

48

00

Both

01

Wired remote controller

Indoor unit fan control for energy saving for cooling

 Enables or disables the power-saving function by controlling the indoor unit fan rotation 
when the outdoor unit is stopped during cooling operation.

(

...  Factory setting)

Function Number

Setting 

Value

Setting Description

49

00

Disable

01

Enable

00: When the outdoor unit is stopped, the indoor unit fan operates continuously following 

the setting on the remote controller.

01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very 

low speed.

Setting record

Record any changes to the settings in the following table.

Setting Description

Setting Value

Filter sign

Auto restart

Room temperature sensor switching

Remote controller custom code

External input control

Room temperature sensor switching (Aux.)

Indoor unit fan control for energy saving for cooling

After completing the FUNCTION SETTING, be sure to turn off the power and turn it on 
again.

11.2. 

Temperature correction 

NOTE:

When changing Function 95, perform this setting before other Room temp. control settings 
(Function 30, 31, 92, 93).
If Function 95 is not set 

fi

 rst, Room temperature control settings (Function 30, 31, 92, 93) 

will be reset and you must re-do them again.

Heat Insulation condition (building insulation)

Heat insulation conditions differ according to the installed environment.
Standard insulation “00” allows system to rapidly respond to the cooling or heating load 
changes.
High insulation “01” is when the heat insulation structure of the building is high and does 
not require system to rapidly respond to cooling or heating load changes.
When High insulation “01” is selected;
• Overheating (overcooling) is prevented at the start-up.
• All room temp. control settings (Function 30, 31, 92, 93) will reset to No correction [0.0°F 

(0.0°C)].

(

...  Factory setting)

Function Number

Setting 

Value

Setting Description

95

00

Standard insulation

01

High insulation

Room temperature control for indoor unit sensor

Depending on the installed environment, correction of the room temperature sensor may 
be required.
Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting “00” 
(manufacturer’s recommended value).
*  When Function 95-01(High insulation) is set, the Standard setting “00” will be the same 

as No correction “01” [0.0°F (0.0°C)].

(

...  Factory setting)

Function Number

Setting 

Value

Setting Description

30

(For cooling)

31

(For heating)

00

Standard setting*

01

No correction 0.0°F (0.0°C)

02

-1°F (-0.5°C)

More 

Cooling 

Less 

Heating

03

-2°F (-1.0°C)

04

-3°F (-1.5°C)

05

-4°F (-2.0°C)

06

-5°F (-2.5°C)

07

-6°F (-3.0°C)

08

-7°F (-3.5°C)

09

-8°F (-4.0°C)

10

+1°F (+0.5°C)

Less 

Cooling 

More 

Heating

11

+2°F (+1.0°C)

12

+3°F (+1.5°C)

13

+4°F (+2.0°C)

14

+5°F (+2.5°C)

15

+6°F (+3.0°C)

16

+7°F (+3.5°C)

17

+8°F (+4.0°C)

Room temperature control for wired remote controller sensor

Depending on the installed environment, correction of the wire remote temperature sensor 
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.

(

...  Factory setting)

Function number

Setting 

value

Setting description

92

(For cooling)

93

(For heating)

00

No correction 0.0°F (0.0°C)

01

No correction 0.0°F (0.0°C)

02

-1°F (-0.5°C)

More 

Cooling 

Less 

Heating

03

-2°F (-1.0°C)

04

-3°F (-1.5°C)

05

-4°F (-2.0°C)

06

-5°F (-2.5°C)

07

-6°F (-3.0°C)

08

-7°F (-3.5°C)

09

-8°F (-4.0°C)

10

+1°F (+0.5°C)

Less 

Cooling 

More 

Heating

11

+2°F (+1.0°C)

12

+3°F (+1.5°C)

13

+4°F (+2.0°C)

14

+5°F (+2.5°C)

15

+6°F (+3.0°C)

16

+7°F (+3.5°C)

17

+8°F (+4.0°C)

Setting record

• Record any changes to the settings in the following table.

Setting

Setting Value

Heat Insulation condition (building insulation)

Room temperature control for indoor unit sensor

Cooling
Heating

Room temperature control for wired remote controller sen-
sor

Cooling
Heating

After completing the Function Setting, be sure to turn off the power and turn it on again.

9318739183_IM.indb   10

9318739183_IM.indb   10

11/19/2014   6:04:32 PM

11/19/2014   6:04:32 PM

Summary of Contents for 9318739183

Page 1: ... strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised plat...

Page 2: ...gerant R410A have a different charging port thread diameter to pre vent erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching...

Page 3: ...s or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or s...

Page 4: ...ping cut off the piping outlet cutting groove with a hacksaw CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur Attach the Drain hose insulation to the drain hose Drain hose insulation Drain hose For left piping and left rear piping alig...

Page 5: ...ct with a flame CAUTION Connect the piping so that the control box cover can easily be removed for servic ing when necessary In order to prevent water from leaking into the control box make sure that the pip ing is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a wrench then tighten with a torque wrench See the table below for the flare nut ti...

Page 6: ... m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Connect the conne...

Page 7: ...or simple remote controller Recommended cable length of wired remote controller is 32 ft 10 m Make sure to do insulate of connecting part when extended the cable 10 2 Remote controller cable modification 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable 2 Connect the remote controller cable and connecting cab...

Page 8: ...onnecting cable to control board connector 1 Pass the cable from the hole in the back of indoor unit 2 Connect the cable to the control board connector 3 Hook the cable to the rib connect the cable rib CN6 CN16 CN14 PCB hole Option type Connector No Wired remote controller Simple remote controller CN6 External input CN14 External output CN16 4 Use cable clamper and screw to fasten the cable of wir...

Page 9: ...do not know the air conditioner custom code setting try each of the custom codes A B C D until you find the code which operates the air conditioner STEP 2 Selecting the Function Number and Setting Value 1 Press the SET TEMP buttons to select the function number Press the MODE button to switch between the left and right digits 2 Press the FAN button to proceed to setting the value Press the FAN but...

Page 10: ...nges When High insulation 01 is selected Overheating overcooling is prevented at the start up All room temp control settings Function 30 31 92 93 will reset to No correction 0 0 F 0 0 C Factory setting Function Number Setting Value Setting Description 95 00 Standard insulation 01 High insulation Room temperature control for indoor unit sensor Depending on the installed environment correction of th...

Page 11: ...ress the test run button with the tip of a ballpoint pen etc Transmitter section TEST RUN button To end test operation press the remote controller START STOP button When the air conditioner is running by pressing the TEST RUN button the OPERA TION Lamp and TIMER Lamp will simultaneously flash slowly Using the wired remote control Option For the operation method refer to the operating manual 1 Stop...

Page 12: ... temp sensor error 8 4 Current sensor error 8 6 Discharge pressure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection 9 5 Compressor rotor position detection error 9 7 Outdoor unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Di...

Reviews: