En-10
External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(
♦
... Factory setting)
Function Number
Setting
Value
Setting Description
46
00
Operation/Stop mode
♦
01
(Setting prohibited)
02
Forced stop mode
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
“Wired remote controller” (01). This function will only work if the function setting 42 is set
at “Both” (01)
(
♦
... Factory setting)
Function Number
Setting
Value
Setting Description
48
00
Both
♦
01
Wired remote controller
Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation
when the outdoor unit is stopped during cooling operation.
(
♦
... Factory setting)
Function Number
Setting
Value
Setting Description
49
00
Disable
♦
01
Enable
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
Setting record
Record any changes to the settings in the following table.
Setting Description
Setting Value
Filter sign
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
11.2.
Temperature correction
NOTE:
When changing Function 95, perform this setting before other Room temp. control settings
(Function 30, 31, 92, 93).
If Function 95 is not set
fi
rst, Room temperature control settings (Function 30, 31, 92, 93)
will be reset and you must re-do them again.
Heat Insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
Standard insulation “00” allows system to rapidly respond to the cooling or heating load
changes.
High insulation “01” is when the heat insulation structure of the building is high and does
not require system to rapidly respond to cooling or heating load changes.
When High insulation “01” is selected;
• Overheating (overcooling) is prevented at the start-up.
• All room temp. control settings (Function 30, 31, 92, 93) will reset to No correction [0.0°F
(0.0°C)].
(
♦
... Factory setting)
Function Number
Setting
Value
Setting Description
95
00
Standard insulation
♦
01
High insulation
Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting “00”
(manufacturer’s recommended value).
* When Function 95-01(High insulation) is set, the Standard setting “00” will be the same
as No correction “01” [0.0°F (0.0°C)].
(
♦
... Factory setting)
Function Number
Setting
Value
Setting Description
30
(For cooling)
31
(For heating)
00
Standard setting*
♦
01
No correction 0.0°F (0.0°C)
02
-1°F (-0.5°C)
More
Cooling
Less
Heating
03
-2°F (-1.0°C)
04
-3°F (-1.5°C)
05
-4°F (-2.0°C)
06
-5°F (-2.5°C)
07
-6°F (-3.0°C)
08
-7°F (-3.5°C)
09
-8°F (-4.0°C)
10
+1°F (+0.5°C)
Less
Cooling
More
Heating
11
+2°F (+1.0°C)
12
+3°F (+1.5°C)
13
+4°F (+2.0°C)
14
+5°F (+2.5°C)
15
+6°F (+3.0°C)
16
+7°F (+3.5°C)
17
+8°F (+4.0°C)
Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
(
♦
... Factory setting)
Function number
Setting
value
Setting description
92
(For cooling)
93
(For heating)
00
No correction 0.0°F (0.0°C)
♦
01
No correction 0.0°F (0.0°C)
02
-1°F (-0.5°C)
More
Cooling
Less
Heating
03
-2°F (-1.0°C)
04
-3°F (-1.5°C)
05
-4°F (-2.0°C)
06
-5°F (-2.5°C)
07
-6°F (-3.0°C)
08
-7°F (-3.5°C)
09
-8°F (-4.0°C)
10
+1°F (+0.5°C)
Less
Cooling
More
Heating
11
+2°F (+1.0°C)
12
+3°F (+1.5°C)
13
+4°F (+2.0°C)
14
+5°F (+2.5°C)
15
+6°F (+3.0°C)
16
+7°F (+3.5°C)
17
+8°F (+4.0°C)
Setting record
• Record any changes to the settings in the following table.
Setting
Setting Value
Heat Insulation condition (building insulation)
Room temperature control for indoor unit sensor
Cooling
Heating
Room temperature control for wired remote controller sen-
sor
Cooling
Heating
After completing the Function Setting, be sure to turn off the power and turn it on again.
9318739183_IM.indb 10
9318739183_IM.indb 10
11/19/2014 6:04:32 PM
11/19/2014 6:04:32 PM