5 Function
5.1 Function Code Setting
CAUTION
•
Set the function code
in the following order at first.
(1) C21 (2) P01 (3) F03 (4) L31 (5)P02
Because when you change them, some other function codes synchronize and change.
There is a risk of accident or injury.
Set the function code as follows before beginning magnetic pole position offset tuning.
Code Name
Data
Setting
C21
Unit for Speed Command
Your easy-to-use setting
P01
Motor - Number of poles
Depends on the motor
F03
Maximum Speed
Depends on the motor
L31
Elevator Parameter - Speed
Depends on the elevator
P02
Motor - Rated capacity
Depends on the motor
Code Name
Data
Setting
F04
Rated Speed
Depends on the motor
F05
Rated Voltage at Rated Speed
Depends on the motor
F42
Control Mode
1 (PM motor - Vector control with encoder)
P03
Motor - Rated current
Depends on the motor
P07
Motor - %R1
5.0 (%)
P08
Motor - %X
10.0 (%)
L01
Pulse encoder - System
4
L02
Pulse encoder - Resolution
Depends on the encoder
L36
ASR - P - Constant at high speed
2.0 (It is necessary to adjust)
L38
ASR - P - Constant at low speed
2.0 (It is necessary to adjust)
5.2 Procedure of Magnetic Pole Position Offset Tuning
You have to execute the tuning as follows before driving motor.
Please inquire of the maker if tuning is impossible normally.
1. Tuning Mode (Function code L03)
Tuning mode is selected by function code L03 as follows. Usually, it is selected according to the tuning procedure.
1 : Tuning operation
2 : Tuning operation with wrong wiring detection (Er7 occurs if wrong wiring is detected.)
3 : Tuning operation with checking accuracy (Er7 occurs if tuning accuracy is not good.)
4 : Reserved for particular manufactures (Do not access this function code.)
5 : Reserved for particular manufactures (Do not access this function code.)
2. Tuning Condition
The recommended condition is following.
(1) The rotor is fixed.
If it is impossible to fix the rotor, it is acceptable even if the rotor is free. (In this case, if the torque bias has been
set, cancel it.)
(2) Encoder abnormality detection is effective. (It is effective in the initial condition as follows. L90=1, L91=10%,
L92=0.5)