7.4 Example of Communication Data
This section shows an example of communication data in the standard format (factory default). The example
assumes that the maximum frequency is 60 Hz (F03 = 60) and the number of poles is 4 (P01 = 4).
(1) Example of operation pattern
Figure 7.1 shows an example of an inverter's operation pattern. To drive the inverter according to this operation
pattern, the communication data should be as shown in item (2) below.
Forward
Reverse
Time (s)
1800 r/min
Figure 7.1 Operation Pattern
(2) Communication data (in hexadecimal)
Response: Being stopped
Inverter ready
Commands:
Run command OFF
Speed command 1800 r/min
(30 Hz = 10000 p.u. = 2710h)
IW****.0
00 00
QW****.8
00 00
IW****.1
00 00
QW****.9
00 00
IW****.2
00 00
QW****.10
00 00
IW****.3
00 00
QW****.11
00 00
IW****.4
00 00
QW****.12
27 10
IW****.5
00 00
QW****.13
00 00
IW****.6
00 00
QW****.14
00 00
IW****.7
10 28
QW****.15
00 00
Response: Running forward
during acceleration
Output speed increasing
Commands:
Run forward command
Speed command 1800 r/min
(= 2710h)
IW****.0
00 00
QW****.8
00 00
IW****.1
00 00
QW****.9
00 00
IW****.2
00 00
QW****.10
00 00
IW****.3
00 00
QW****.11
00 00
IW****.4
00 00
QW****.12
27 10
IW****.5
00 00
QW****.13
00 01
IW****.6
** **
QW****.14
00 00
IW****.7
12 21
QW****.15
00 00
Note:
Asterisks (****) denote the station address of the SX-bus communications card.