Response: Running forward
Arrived at the reference speed
Commands:
Run forward command
Speed command 1800 r/min
(= 2710h)
IW****.0
00 00
QW****.8
00 00
IW****.1
00 00
QW****.9
00 00
IW****.2
00 00
QW****.10
00 00
IW****.3
00 00
QW****.11
00 00
IW****.4
00 00
QW****.12
27 10
IW****.5
00 00
QW****.13
00 01
IW****.6
** **
QW****.14
00 00
IW****.7
10 21
QW****.15
00 00
Response: Running forward
during deceleration
Output speed decreasing
Commands:
Run command OFF
Speed command 1800 r/min
(= 2710h)
IW****.0
00 00
QW****.8
00 00
IW****.1
00 00
QW****.9
00 00
IW****.2
00 00
QW****.10
00 00
IW****.3
00 00
QW****.11
00 00
IW****.4
00 00
QW****.12
27 10
IW****.5
00 00
QW****.13
00 00
IW****.6
** **
QW****.14
00 00
IW****.7
14 21
QW****.15
00 00
Response: Being stopped
Inverter ready
Command:
Run command OFF
Change the speed command
to 300 r/min.
(1667 p.u. = 0683h)
IW****.0
00 00
QW****.8
00 00
IW****.1
00 00
QW****.9
00 00
IW****.2
00 00
QW****.10
00 00
IW****.3
00 00
QW****.11
00 00
IW****.4
00 00
QW****.12
06 83
IW****.5
00 00
QW****.13
00 00
IW****.6
00 00
QW****.14
00 00
IW****.7
30 28
QW****.15
00 00
Note: