12
V815 OPERATING INSTRUCTIONS
General Specifications
Item Model
AC Power Supply
DC Power Supply
Compatible
Specification
CE marking
-
EN61000-6-2, EN61000-6-4
UL/cUL
UL508
Rated Voltage
100 - 240 VAC
24 VDC
Permissible Range of Voltage
-15 %,
+
10 %
±
10 %
Permissible Momentary Power Failure Within 20 ms
24 VDC: Within 1 ms
Power Consumption (Maximum
Rating)
0 VA or less
40 W or less
Rush Current
100 VAC: 20 A or less (10 ms or less)
200 VAC: 40 A or less (10 ms or less)
30 A or less (1 ms or less)
Withstand Voltage
AC external terminals to FG:
1500 VAC per minute
DC external terminals to FG:
500 VAC per minute
Insulation Resistance
500 VDC, 10 M
Ω
or above
Surrounding Air Temperature
0
°
C to +40
°
C
*1
Storage Surrounding Air Temperature
-
10
°
C to +50
°
C
*1
Surrounding Air Humidity
85 % RH or less (without dew condensation)
*1
Storage Surrounding Air Humidity
85 % RH or less (without dew condensation)
*1
Altitude
2000 m or lower
Atmosphere
No corrosive gas, no excessive dust, and no conductive dust
Vibration Resistance
Vibration frequency: 10 to 150 Hz, Acceleration: .8 m/s
2
(1.0 G),
Half-amplitude: 0.075 mm, 3 directions of X, Y and Z: one hour
Shock Resistance
Pulse shape: Sine half wave
Peak acceleration: 147 m/s
2
(15 G), 3 directions of X, Y and Z: 6 times
Noise Resistance
1500 Vp-p
(pulse width 1
µ
s, rising time: 1 ns)
1000 Vp-p
(pulse width 1
µ
s, rising time: 1 ns)
Static Electricity Discharge
Resistance
Compliant with IEC61000-4-2, Contact: 6 kV, Air: 8 kV
Pollution Degree
*2
For use in Pollution Degree 2
Grounding
Less than 100
Ω
, FG/SG connected
Structure
Protection structure : front panel complies with IP65 (when using gasket)
rear case complies with IP20
Form
: in a body
Mounting procedure : inserted in a mounting panel
Sheet metal thickness : 2 to 5 mm
*3
Cooling System
Cooling naturally
Weight
Approx. 5.5 kg
Approx. 5.3 kg
Dimensions W
×
H
×
D
382.8
×
312.8
×
81.1 mm
Panel Cut-out Dimensions
36.4
+0.5
-
0
×
2.4
+0.5
-
0
mm
Material
Aluminum
*1 Wet-bulb temperature 3 °C or less
*2 This index indicates the degree to which conductive material is generated in the environment where the
equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to
condensation.
*3 It is recommended to use the mounting panel whose thickness is 3.0 mm or more to keep the unit compliant with
IP65.