2-17
Section 2 Specifications
Status indication LED
Status
Specification
PWR of analog input/output unit
ON (red)
While 5V DC power is normally supplied.
(2) Functions
1) Status indication LED
2) Terminal block
These are terminals for 24V DC power supply to operate the analog unit and analog input signal.
* For the wiring method, refer to “2-4 Wiring.”
Digital value range
JP1 setting
-8192 to 8191
0 to 16383
3) JP1: Digital value range selection
This jumper pin is used to set the digital value range for analog output (upper side) and analog input (lower side)
U
B
Analog output
Analog input
U
B
Analog output
Analog input
Signal range
JPA setting
JPB setting
0 to 10V
-10 to 10V
0 to 5V
-5 to 5V
0 to 20mA
-20 to 20mA
0 to 10mA
-10 to 10mA
4) JPA and 5) JPB: Analog output range selection