![Fuji Electric MICREX-SX series SPF User Manual Download Page 10](http://html1.mh-extra.com/html/fuji-electric/micrex-sx-series-spf/micrex-sx-series-spf_user-manual_2341797010.webp)
2-3
Section 2 Specifications
Item
Specification
Type
NA0AY02-MR
No. of output channels
2 channels
External load resistance
Voltage output: 500
W
to 1 M
W
, Current output: 0 to 500
W
or less
Analog output range
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
Resolution
14 bits
Overall accuracy
±1%
Data type of digital input value INT type
Output period
Synchronized with the scan of the basic unit.
External wire connections
8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire size
AWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication
5V power supply display, ON when normal (red)
Isolation method
Transducer (power supply) and photocoupler (signal)
Occupied words
2 words
External power supply
24V DC, 90mA
Internal current consumption
5V DC, 33mA
Dimensions
40 (W) x 90 (H) x 80 (D) (mm)
Mass
Approx. 140g
(2) Analog output unit