1-39
The system also checks these conditions. The following must be met before jug fill is allowed.
Solenoid closed
Orange fill button pressed longer than 3 sec.
Waste valve closed
Filter Now? Yes/No, Confirm Yes/No, or Skim Vat cannot be displayed
System power cycle (all boards – controllers, MIB, AIF and ATO) after changing setup from JIB to Bulk (use
momentary reset). Ensure reset is pressed and held for at least ten seconds.
No filtration or other filter menu selection can be in process.
Other factors that may not allow fill jug from bulk –
Defective solenoid
Defective switch
Bulk fresh oil pump issue
Bulk fresh oil relay issue
If using multiple fryer systems that are both attached to the bulk fresh oil system, they may not be able to fill both
units at the same time if they have a bulk fresh oil unit with a single head. Some bulk fresh oil units have dual heads
which can fill more than one fryer simultaneously.
1.17 AIF (Automatic Intermittent Filtration) Service Procedures
The AIF (Automatic Intermittent Filtration) board controls
the actuators that open and close the drain and return valve.
The AIF boards are located inside a protective housing
under each frypot (see Figure 15).
Figure 15
1.17.1 AIF (Automatic Intermittent Filtration) Troubleshooting
Problem
Probable Causes
Corrective Action
Actuator doesn’t
function.
A.
No power to the AIF board.
B.
Actuator is unplugged.
A.
Check pins 5 and 6 of J2 at the MIB
board. Should read 24VDC. Check
voltage on pins 5 and 6 at the other
end of harness and ensure 24VDC is
present. Continue to check pins 5 and
6 for 24VDC on plugs J4 and J5 on the
AIF boards.
B.
Ensure the actuator is plugged into the
proper connection (J1 for FV return, J3
for DV return and J6 for FV drain and
J7 for DV drain).
Summary of Contents for FilterQuick FQG30
Page 8: ...1 3 ...
Page 41: ...1 36 1 16 2 Bulk Wiring ...
Page 56: ...1 51 1 18 6 Clogged Drain Failed Oil Sensor Error Flowchart ...
Page 57: ...1 52 1 18 7 Menu Trees 1 18 7 1 FilterQuick Controller Setup Menu Tree ...
Page 58: ...1 53 1 18 7 2 FilterQuick Filter and Info Mode Menu Tree ...
Page 62: ...1 57 1 20 Principal Wiring Connections ...
Page 63: ...1 58 1 21 Wiring Diagrams 1 21 1 Main FQG 230 430 120V CE Export ...
Page 64: ...1 59 1 21 2 Main FQG 230 430 Australia ...
Page 65: ...1 60 1 21 3 Main FQG 230 430 120V CE Export with Solid Shortening ...
Page 66: ...1 61 1 21 4 Main FQG 230 430 Australia with Solid Shortening ...
Page 67: ...1 62 1 21 5 Main FQG 330 530 120V CE Export ...
Page 68: ...1 63 1 21 6 Main FQG 330 530 Australia ...
Page 69: ...1 64 1 21 7 Main FQG 330 530 120V CE Export with Solid Shortening ...
Page 70: ...1 65 1 21 8 Main FQG 330 530 Australia with Solid Shortening ...
Page 71: ...1 66 1 21 9 Transformer Filter Box 430 530 ...
Page 73: ...1 68 1 22 2 FilterQuick FQG30 Series Simplified Wiring with Push Buttons ...
Page 74: ...1 69 1 22 3 FilterQuick FQG30 Series Data Network Flowchart ...
Page 76: ...1 71 1 24 Shortening Melting Unit Wiring Diagram ...
Page 77: ...1 72 1 25 Modular Basket Lift Wiring Diagram 100 120V ...
Page 78: ...1 73 1 26 Modular Basket Lift Wiring Diagram 208 250V ...