Requirements for the S0 meter:
-
Must meet standard IEC 62053-31 Class B
-
Max. voltage: 15 V DC
-
Max. current when ON: 15 mA
-
Min. current when ON: 2 mA
-
Max. current when OFF: 0.15 mA
Recommended max. impulse rate of S0 meter:
PV power kWp [kW]
Max. impulse rate per kWp
30
1000
20
2000
10
5000
≤
5.5
10000