107
EN
Technical data
Fronius Agilo
Outdoor 75.0-3
Input data
Output data
General data
Protection devices
MPP voltage range
460 - 820 V DC
Max. input voltage
(at 1000 W/m²/ -10 °C in an open circuit)
950 V DC
Max. input current
170.0 A
Max. short circuit current of the solar modules
255.0 A
Nominal output power (P
nom
)
75 kVA
Max. output power
75 kVA
Nominal grid voltage
3~NPE 400 V / 230 V
Mains voltage tolerance
+10 / -5 %
1)
Nominal output current (three-phase)
112.4 A
Nominal frequency
50 - 60 Hz
1)
Total harmonic distortion
< 3 %
Power factor cos phi
1
0.8 - 1 ind./cap.
2)
Max. permitted mains impedance Z
max
at PCC
3)
66 mOhm
Max. feedback current
4)
0 A
5)
Starting current pulse
6)
0 A
5)
Max. output fault current per period
522 A / 2.47 ms)
Maximum efficiency
97.3 %
Europ. efficiency
96.7 %
Overnight self-consumption
36 W
Cooling
Controlled forced-air ventila-
tion
Degree of protection
IP 44
Dimensions l x w x h
1205 x 863 x 1914 mm
Weight
732 kg
Permitted ambient temperature
(4 - 100 % condensing)
- 25 °C - +50 °C
EMC emission class
A
Overvoltage category AC / DC
3 / 2
Degree of pollution
3
DC insulation measurement
Warning/shutdown
7)
at R
ISO
< 31.66 kOhm
Manifestation of DC overload
Operating point shift
power limitation
DC disconnector
Integrated
Summary of Contents for Agilo 100.0-3
Page 2: ...0...
Page 4: ...2...
Page 8: ...6...
Page 13: ...General information...
Page 14: ......
Page 30: ...28...
Page 31: ...Installation and commissioning...
Page 32: ......
Page 51: ...49 EN 1 2 Inserting the fuse grounds the solar modules on the negative pole 1 1 1 2 2...
Page 53: ...51 EN 2 3 Tightening torque 3 Nm 1 3 2 4 5 4 3 2 4 5 1 5...
Page 57: ...Operation...
Page 58: ......
Page 84: ...82...
Page 85: ...Troubleshooting and maintenance...
Page 86: ......
Page 107: ...Appendix...
Page 108: ......